| 2016-01-22 17:00:18 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010668 |
| | ADD: 2401 EMBASSY DR. |
| | CONT: LEO ROOFING |
| | TEL: 561-935-4979 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JAN. 22/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) WIND EXPOSURE TO THE N. W. IS A EXPOSURE D NOT A B. |
| | 2014 FBC-B 1609.4.3 EXPOSURE CATEGORY D. EXPOSURE D |
| | SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS |
| | DEFINED BY SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND |
| | DIRECTION FOR A DISTANCE OF AT LEAST 5,000 FEET (1524 |
| | M) OR 20 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS |
| | GREATER. EXPOSURE D SHALL ALSO APPLY WHERE THE GROUND |
| | SURFACE ROUGHNESS IMMEDIATELY UPWIND OF THE SITE IS B |
| | OR C, AND THE SITE IS WITHIN A DISTANCE OF 600 FEET |
| | (183 M) OR 20 TIMES THE BUILDING HEIGHT, WHICHEVER IS |
| | GREATER, FROM AN EXPOSURE D CONDITION AS DEFINED IN THE |
| | PREVIOUS SENTENCE. |
| | |
| | 2) THE FL 7804-R8 ENTEGRA ROOF TILE REPORT PAGE 2 DID |
| | NOT IDENTIFY WHICH FLAT TILE IS TO BE INSTALLED. TABLES |
| | 1 & 2 WERE NOT CIRCLED AS TO AERODYNAMIC MULTIPLIERS, |
| | RESTORING MOMENT, DIRECT DECK, ROOF SLOPE. TABLE 3A-2 |
| | ALSO NOT FILED OUT. |
| | |
| | 3) THE FL 6332-R4 3M ROOF TILE ADHESIVE TABLE 1, TABLE |
| | 2 AND PADDY PLACEMENT ON PAGE 5 OF 6 IS NOT IDENTIFIED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |