| 2016-05-05 13:21:44 | 1) THE ZURN SPECIFICATION SHEET SHOWS A 3 INCH INLET | | | AND OUTLET BUT THE PLUMBING SANITARY RISER SHOWS A 2 | | | INCH INLET AND OUTLET. CLARIFY. | | | 2) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE SIDE OF | | | THE GREASE TRAP PER CITY ORD. | | | 3) THE SANITARY RISER FOR THE NEW PLUMBING ( FLOOR | | | SINKS, PROPOSED HAND SINK, REROUTED FLOOR SINK, ETC.) | | | DOES NOT COMPLY WITH 2014 FPC SEC.905.3 FOR THE WAY THE | | | VENTS CONNECT TO THE DRAINAGE SYSTEM. SUBMIT A SANITARY | | | RISER THAT COMPLIES WITH THE 2014 FPC. | | | 4) THE PLANS NEED TO BE COMPILED INTO TWO COMPLETE SETS | | | FOR SUBMITTAL. FBC 107.1. | | | 5) THE GAS SHALL BE SUBMITTED UNDER A SEPARATE. | | | 6) THE WATER RISER STILL SHOWS THE TANKLESS WATER | | | HEATER AS EXISTING. IT IS NOT EXISTING. IT IS NEW. IT | | | REPLACED AN EXISTING ELECTRIC TANKLESS WATER HEATER. | | | SHOW IT AS NEW ON THE RISER. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|