Plan Review Notes
Plan Review Notes For Permit 16010661
Permit Number 16010661
Review Stop P
Sequence Number 2
Notes
Date Text
2016-03-23 13:59:271) THE TANKLESS WATER HEATER WAS SHOWN AS ELECTRIC ON
 THE PLANS FOR PERMIT # 11090836 FOR THIS SPACE.THE
 WATER HEATER WAS ALSO SHOWN ON THE OPPOSITE SIDE OF THE
 SPACE THAN WHERE IT IS NOW. CITY RECORDS DO NOT SHOW
 ANY ADDITIONAL PERMITS FOR THE RELOCATION OF THE
 TANKLESS WATER HEATER NOR FOR THE INSTALLATION OF THE
 GAS. THEREFORE, THE GAS TANKLESS WATER HEATER SHALL NOT
 BE NOTED AS EXISTING ON THE PLANS, IT SHALL BE SHOWN AS
 NEW SINCE IT WAS NEVER PERMITTED AND SHALL BE INCLUDED
 IN THIS SCOPE OF WORK. FBC 105.1.SEE COPIES OF FLOOR
 PLAN IN FOLDER. THE SUBMITTED PICTURE SHOWS A FAIRLY
 NEW TANKLESS WATER HEATER.
 2) SINCE THIS IS A CHANGE OF OCCUPANCY AND COMBINATION
 OF SPACE, THE PLANS WILL BE REQUIRED TO BE REVIEWED BY
 THE DEPT. OF BUSINESS AND PROFESSIONAL REGULATION,
 DIVISION OF HOTELS AND RESTAURANTS. SECOND REQUEST.
 3) SHT. LS-1 SHOWS THE OCCUPANT LOAD AS 150 PERSONS ON
 THE PLUMBING FIXTURE CALCULATION TABLE AND ALSO ON THE
 PLAN. I DO NOT SEE WHERE THE SEATS AND BENCH LOCATED ON
 THE EXTERIOR OF THE BUILDING ON THE SOUTH END OF THE
 STRUCTURE HAVE BEEN INCLUDED IN THE OCCUPANT LOAD.
 CLARIFY.SUBMIT A TOTAL OCCUPANT LOAD.
 4) THE NEW FLOOR SINKS ARE STILL NOT VENTED IN
 ACCCORDANCE WITH2014 FBC, PLUMBING SEC.901.2.1.
 5) SEE THE FOLLOWING REQUIREMENTS FOR A PROPER GAS
 REVIEW FOR THE GAS TANKLESS WATER HEATER.
  
 A).SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 B.)SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
 C)TYPE OF GAS (LP OR NATURAL).
 D) BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
 E)SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 F)SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
 G)INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON
 THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
 H)SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505 OR 2014 FBC-RES. SEC.G2426.
 I)SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
 6) SHT. P-1 - FLOW RATE CALCULATIONS - UNDER THE
 MULTIPLE FIXTURE DESIGN- EXPLAIN WHY ONLY 50% OF THE 2
 COMPARTMENT SINK IS BEING ADDED TO THE FLOW RATE
 INSTEAD OF THE CALCULATED FLOW RATE OF 22.85 GPM.
 7) SUBMIT A MANUFACTURER'S INSTALLATION MANUAL FOR THE
 GREASE INTERCEPTOR.WHERE IS THE VENTED INLET FLOW
 CONTROL DEVICE ON THE GREASE INTERCEPTOR?
 8) SHT. A-1 SHOWS THE GREASE INTERCEPTOR LOCATED IN THE
 WALK IN COOLER. THE SIZE, TYPE AND LOCATION OF EACH
 INTERCEPTOR SHALL BE APPROVED BY THE PLUMBING OFFICIAL
 PER 2014 FPC SEC.1003.2.PLEASE EXPLAIN HOW THIS
 LOCATION MAKES THE INTERCEPTOE ACCESSIBLE FOR
 MAINTENANCE AND REPAIR.
 (9 THE FOLLOWING TEXT IS FROM THE CWPB CODE OF
 ORDINANCES SEC.90-125 (7)
 INTERCEPTORS ARE TO BE INSTALLED OUTSIDE OF THE FOOD
 PREPARATION AREA WITH THE DISHWASHER DISCHARGING VIA A
 SEPARATE LINE.
 EACH INTERCEPTOR SHALL BE SO INSTALLED AS TO PROVIDE
 READY ACCESSIBILITY TO THE COVER, AND MEANS FOR
 SERVICING AND MAINTAINING THE INTERCEPTOR IN WORKING
 AND OPERATING CONDITION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  