Plan Review Notes
Plan Review Notes For Permit 16010661
Permit Number 16010661
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-28 10:15:161) THE PLANS NOTE THIS OCCUPANCY AS "MERCANTILE." THE
 PROPER OCCUPANCY CLASSIFICATION IS A-2 BASED ON THE
 OCCUPANT LOAD PER THE 2014 FBC SEC. 303.3. SINCE THIS
 WILL BE A CHANGE OF OCCUPANCY, COMPLIANCE WITH CHAPTER
 10 OF THE 2014 FBC-EXISTING BUILDING IS ALSO REQUIRED.
 2) SHT.LS-1 - THERE IS A NOTE ON THE PLAN NEXT TO ONE
 OF THE TABLES THAT READS" PROPOSED SERVICE SINK" BUT
 NOTHING IS SHOWN. CLARIFY.A SERVICE SINK IS REQUIRED BY
 2014 FBC TABLE 403.1.
 3) THIS SPACE ALSO HAS OUTDOOR SEATING ON THE FRONT AND
 ALSO ON THE SIDE. THESE SEATS SHALL ALSO BE INCLUDED IN
 THE OCCUPANT LOAD OF THE SPACE.FBC-PLUMBING
 SEC.403.1.4.
 4) SHT. LS-1 - THE PLUMBING FIXTURE CALCULATION TABLE
 SHOWS 4 WATER CLOSETS AND FOUR LAVATORIES BEING
 PROVIDED FOR THE MALES AND FEMALES WHEN IN THE FACT THE
 FIXTURE COUNT IS TWO WATER CLOSETS AND TWO LAVATORIES
 FOR THE MALES AND FEMALES. REVISE THE TABLE TO REFLECT
 THE CORRECT FIXTURE COUNT FOR THE OCCUPANT LOAD.
 5) SINCE THIS IS A CHANGE OF OCCUPANCY AND COMBINATION
 OF SPACE, THE PLANS WILL BE REQUIRED TO BE REVIEWED BY
 THE DEPT. OF BUSINESS AND PROFESSIONAL REGULATION,
 DIVISION OF HOTELS AND RESTAURANTS.
 6) THE ICE MACHINE SHALL BE EQUIPPED WITH A BACKFLOW
 PREVENTER ON THE WATER SUPPLY LINE PER THE 2014
 FBC-PLUMBING SEC.608.3.
 7) SUBMIT REVISED CALCULATIONS AND THE CAPACITY OF THE
 EXISTING GREASE INTERCEPTOR TO ENSURE THAT THE EXISTING
 INTERCEPTOR HAS THE CAPACITY TO HANDLE THE ADDITIONAL
 LOAD FROM THE ADDED SPACE.2014 FBC-PLUMBING SEC.1003.2.
 8) ALL SINKS/LAVATORIES SHALL BE EQUIPPED WITH HOT
 WATER PER THE 2014 FBC-PLUMBING SEC. 607.1.
 9) CLEANOUTS ARE REQUIRED IN THE BASE OF WASTE STACKS
 PER 2014 FBC-PLUMBING SEC.708.3.4.
 10) THE DRAIN FOR THE ESPRESSO MACHINE IS NOT VENTED.
 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 TANKLESS WATER HEATER.
 12) THE NEW FLOOR SINKS SHALL BE TRAPPED PER 2014 FBCP
 SEC.802.2.
 13) SHT.E-2 - ELECTRIC PANEL B2 SHOWS THE TANKLESS
 WATER HEATER AS GAS. SUBMIT A GAS PIPING RISER DIAGRAM
 FOR REVIEW. PERMIT #11120186 SHOWS THIS TANKLESS WATER
 HEATER AS ELECTRIC. CLARIFY.
 14) SHOW THE PIPE SIZES ON THE WATER RISER.
 15) SHT. P-1 - THERE IS A REROUTED EXISTING FLOOR SINK
 ON THE RISER DIAGRAM THAT APPEARS TO CONNECT NOWHERE.
 CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  