| 2016-01-28 10:15:16 | 1) THE PLANS NOTE THIS OCCUPANCY AS "MERCANTILE." THE |
| | PROPER OCCUPANCY CLASSIFICATION IS A-2 BASED ON THE |
| | OCCUPANT LOAD PER THE 2014 FBC SEC. 303.3. SINCE THIS |
| | WILL BE A CHANGE OF OCCUPANCY, COMPLIANCE WITH CHAPTER |
| | 10 OF THE 2014 FBC-EXISTING BUILDING IS ALSO REQUIRED. |
| | 2) SHT.LS-1 - THERE IS A NOTE ON THE PLAN NEXT TO ONE |
| | OF THE TABLES THAT READS" PROPOSED SERVICE SINK" BUT |
| | NOTHING IS SHOWN. CLARIFY.A SERVICE SINK IS REQUIRED BY |
| | 2014 FBC TABLE 403.1. |
| | 3) THIS SPACE ALSO HAS OUTDOOR SEATING ON THE FRONT AND |
| | ALSO ON THE SIDE. THESE SEATS SHALL ALSO BE INCLUDED IN |
| | THE OCCUPANT LOAD OF THE SPACE.FBC-PLUMBING |
| | SEC.403.1.4. |
| | 4) SHT. LS-1 - THE PLUMBING FIXTURE CALCULATION TABLE |
| | SHOWS 4 WATER CLOSETS AND FOUR LAVATORIES BEING |
| | PROVIDED FOR THE MALES AND FEMALES WHEN IN THE FACT THE |
| | FIXTURE COUNT IS TWO WATER CLOSETS AND TWO LAVATORIES |
| | FOR THE MALES AND FEMALES. REVISE THE TABLE TO REFLECT |
| | THE CORRECT FIXTURE COUNT FOR THE OCCUPANT LOAD. |
| | 5) SINCE THIS IS A CHANGE OF OCCUPANCY AND COMBINATION |
| | OF SPACE, THE PLANS WILL BE REQUIRED TO BE REVIEWED BY |
| | THE DEPT. OF BUSINESS AND PROFESSIONAL REGULATION, |
| | DIVISION OF HOTELS AND RESTAURANTS. |
| | 6) THE ICE MACHINE SHALL BE EQUIPPED WITH A BACKFLOW |
| | PREVENTER ON THE WATER SUPPLY LINE PER THE 2014 |
| | FBC-PLUMBING SEC.608.3. |
| | 7) SUBMIT REVISED CALCULATIONS AND THE CAPACITY OF THE |
| | EXISTING GREASE INTERCEPTOR TO ENSURE THAT THE EXISTING |
| | INTERCEPTOR HAS THE CAPACITY TO HANDLE THE ADDITIONAL |
| | LOAD FROM THE ADDED SPACE.2014 FBC-PLUMBING SEC.1003.2. |
| | 8) ALL SINKS/LAVATORIES SHALL BE EQUIPPED WITH HOT |
| | WATER PER THE 2014 FBC-PLUMBING SEC. 607.1. |
| | 9) CLEANOUTS ARE REQUIRED IN THE BASE OF WASTE STACKS |
| | PER 2014 FBC-PLUMBING SEC.708.3.4. |
| | 10) THE DRAIN FOR THE ESPRESSO MACHINE IS NOT VENTED. |
| | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | TANKLESS WATER HEATER. |
| | 12) THE NEW FLOOR SINKS SHALL BE TRAPPED PER 2014 FBCP |
| | SEC.802.2. |
| | 13) SHT.E-2 - ELECTRIC PANEL B2 SHOWS THE TANKLESS |
| | WATER HEATER AS GAS. SUBMIT A GAS PIPING RISER DIAGRAM |
| | FOR REVIEW. PERMIT #11120186 SHOWS THIS TANKLESS WATER |
| | HEATER AS ELECTRIC. CLARIFY. |
| | 14) SHOW THE PIPE SIZES ON THE WATER RISER. |
| | 15) SHT. P-1 - THERE IS A REROUTED EXISTING FLOOR SINK |
| | ON THE RISER DIAGRAM THAT APPEARS TO CONNECT NOWHERE. |
| | CLARIFY. |
| | |
| | PLUMBING PLAN REVIEW |