| Plan Review Notes For Permit 16010661 |
| Permit Number |
16010661 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-25 18:31:53 | FBC 2014 5TH ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 516-805-6700 | | | [email protected] | | | ALTERNATE CONTACT | | | MIKE ALBARRAN | | | 561-805-6746 | | | [email protected] | | | | | | PROVISO : | | | | | | -AT LEAST ONE RECEPTACLE OUTLET | | | SHALL BE INSTALLED WITHIN 450 MM (18 IN.) OF THE TOP OF | | | A | | | SHOW WINDOW FOR EACH 3.7 LINEAR M (12 LINEAR FT) OR | | | MAJOR | | | FRACTION THEREOF OF SHOW WINDOW AREA MEASURED | | | HORIZONTALLY | | | AT ITS MAXIMUM WIDTH. NEC 210.62 | | | | | | -NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN | | | 25? OF MECHANICAL EQUIPMENT. | | | | | | -NEC 600.5(A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL | | | BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO | | | PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE OUTLET | | | IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH | | | TENANT SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE. | | | THE OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT | | | RATED AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD. | | | SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED | | | ACCESSIBLE TO PEDESTRIANS. |
|