| Plan Review Notes For Permit 16010555 |
| Permit Number |
16010555 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-28 13:51:31 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1) DESIGN PROFFESIONAL FOR A COMMERCIAL SIGN MUST BE | | | EITHER BE A LICENSED ENGINEER OR ARCHITECT PER FLORIDA | | | STATUE 471 & 481 | | | | | | 2) SIGN SHALL BE SUPPLIED BY A MINIMUM DEDICATED 20 AMP | | | BRANCH CIRCUIT ACCORDING TO NEC 600.5(A). IF EXISTING | | | PLEASE MARK ON PLANS ! | | | - SECOND REQUEST, NOT ADDRESSED. | | | | | | 3) FBC-E SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS. | | | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. | | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | | FOR A PERIOD OF AT LEAST 10 HOURS. PLEASE ADD A NOTE ! | | | - SECOND REQUEST, NOT ADDRESSED |
|