2016-07-28 13:51:31REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1) DESIGN PROFFESIONAL FOR A COMMERCIAL SIGN MUST BE
 EITHER BE A LICENSED ENGINEER OR ARCHITECT PER FLORIDA
 STATUE 471 & 481
  
 2) SIGN SHALL BE SUPPLIED BY A MINIMUM DEDICATED 20 AMP
 BRANCH CIRCUIT ACCORDING TO NEC 600.5(A). IF EXISTING
 PLEASE MARK ON PLANS !
 - SECOND REQUEST, NOT ADDRESSED.
  
 3) FBC-E SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. PLEASE ADD A NOTE !
 - SECOND REQUEST, NOT ADDRESSED