| Plan Review Notes For Permit 16010552 |
| Permit Number |
16010552 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-07-28 14:49:55 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | EAST ELEVATION ORIGINAL PLANS WERE PASSED WITH A | | | PROVISO WITH FBC-E SECTION C405.2.4 EXTERIOR LIGHTING | | | CONTROLS ( MARKED ON PLANS ) , 2ND SUBMITTAL IS MISSING | | | THIS NOTE PLEASE COMPLY. | | | | | | 1) LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A | | | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME | | | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION | | | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR | | | PHOTOSENSOR. | | | ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING | | | PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER | | | FOR A PERIOD OF AT LEAST 10 HOURS. FBC-E SECTION | | | C405.2.4 PLEASE ADD THIS NOTE ! | | | | | | 2) DESIGN PROFFESIONAL FOR A COMMERCIAL SIGN SHALL BE A | | | LICENSED ENGINEER OR ARCHITECT PER FLORIDA STATUE 471 & | | | 481 | | | | | | |
|