2016-01-20 06:09:131) THE PIPING SCHEMATIC THAT WAS SUBMITTED DOES NOT
 SHOW ANY PIPE SIZES.SIZE ALL PIPING ON THE SCHEMATIC
 AND SHOW THE TYPE OF PIPE MATERIAL.. WPB AMENDMENTS TO
 FBC SEC. 107.2.1.
 2) THE ARE LETTERS ON THE PIPING SCHEMATIC IDENTIFYING
 THE SPECIFIC PARTS BUT THERE IS NO LEGEND EXPLAINING
 WHAT THESE ITEMS SRE. I CANNOT PERFORM A COMPREHENSIVE
 REVIEW WHEN THE PLANS LACK SUCH INFORMATION.
  