| Plan Review Notes For Permit 16010539 |
| Permit Number |
16010539 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-21 11:25:21 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010539 | | | 1/21/16 | | | | | | 1) THE PLAN INDICATES 300 CFM'S OF AIR BEING RETURNED | | | FROM THE BEDROOM WHERE ONLY 196 CFM'S OF AIR IS BEING | | | SUPPLIED- PLEASE CORRECT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|