Plan Review Notes For Permit 16010532
Permit Number 16010532
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-04 15:33:401ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. SHEET E1.0 MARK ON DEMO PLANS THE POLES BEING
 REMOVED.
 2. SHEET ES1.1 YOU NEED TO INDICATE ON THE PLANS THE
 LOCATION OF THE POWER SOURCE FOR THE SITE LIGHTING.
 3. SHEET ES1.1 PER FBC-EC405.2.4 EXTERIOR LIGHTING
 CONTROLS COMPLIANT WITH THIS SECTION IS MANDATORY.
 4. SHEET ES1.1 EXTERIOR LIGHTING SHALL COMPLY WITH
 FBC-EC405.6 YOU NEED TO SUBMIT A LIGHTING POWER DENSITY
 ALLOWANCE CHART TO INDICATE COMPLIANCE.
 5. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE
 ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN
 FOR INSPECTION. NOT SITE TUBES WILL BE ALLOWED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  