| Plan Review Notes For Permit 16010532 |
| Permit Number |
16010532 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-04 15:33:40 | 1ST ELECTRICAL REVIEW NOTES: | | | REVIEWED FOR COMPLIANCE WITH: | | | FBC 5TH EDITION 2014 | | | NFPA 70 2011 (NEC) | | | | | | CORRECTIONS REQUIRED: | | | 1. SHEET E1.0 MARK ON DEMO PLANS THE POLES BEING | | | REMOVED. | | | 2. SHEET ES1.1 YOU NEED TO INDICATE ON THE PLANS THE | | | LOCATION OF THE POWER SOURCE FOR THE SITE LIGHTING. | | | 3. SHEET ES1.1 PER FBC-EC405.2.4 EXTERIOR LIGHTING | | | CONTROLS COMPLIANT WITH THIS SECTION IS MANDATORY. | | | 4. SHEET ES1.1 EXTERIOR LIGHTING SHALL COMPLY WITH | | | FBC-EC405.6 YOU NEED TO SUBMIT A LIGHTING POWER DENSITY | | | ALLOWANCE CHART TO INDICATE COMPLIANCE. | | | 5. UNLESS PRIOR ARRANGEMENTS ARE MADE WITH THE | | | ELECTRICAL INSPECTOR, ALL TRENCHING SHALL REMAIN OPEN | | | FOR INSPECTION. NOT SITE TUBES WILL BE ALLOWED. | | | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | | CITY RE-SUBMITTAL FORM. CLOUDING THE CHANGES WILL BE | | | GREATLY APPRECIATED. | | | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | | CONTACT ME DIRECTLY. | | | | | | THANK YOU, | | | MIKE ALBARRAN | | | ELECTRICAL PLANS EXAMINER | | | PH: 561-805-6746 | | | EMAIL: [email protected] | | | |
|