| 2016-12-05 11:42:34 | RESIDENTIAL (R3) ALTERATION SIXTH BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- NEW ENERGY CALCULATIONS SUBMITTED (FORM R405-2014): |
| | A) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. SEC. |
| | R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | B) CLARIFY WHY THE COOLING SYSTEM IS ONLY 12.8 KBTU/HR, |
| | SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | C) ATTIC INFORMATION ON PAGE 2 OF 4 SPECIFIES A VENT |
| | RATIO OF 1/300. TYPICALLY, THE VENTILATION RATIO IS |
| | 1/150. IN ORDER TO USE THE 1/300 VENT RATIO, THE |
| | ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE DETAILS |
| | AND SPECIFICATIONS SHOWING COMPLIANCE AS REQUIRED BY |
| | THE EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL, 5TH |
| | EDITION (2014). OTHERWISE, REVISE THE VENT RATIO TO |
| | 1/150. |
| | |
| | D) THE EPL DISPLAY CARD NEEDS TO BE SIGNED BY THE |
| | BUILDER. ONLY THE NAME OF THE BUILDER WAS PROVIDED. THE |
| | SIGNATURE DOESN'T MATCH SIGNATURE SHOWN ON THE PERMIT |
| | APPLICATION. SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH |
| | EDITION (2014). |
| | |
| | E) ENGINEER OF RECORD COMPLETING THE ENERGY |
| | CALCULATIONS TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS |
| | REQUIRED BY CHAPTER 471 F.S WHEN SUBMITTING |
| | DOCUMENTATION FOR PUBLIC RECORDS. |
| | |
| | NOTE: |
| | LABELS FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND |
| | SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ARE |
| | REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT TAKING |
| | THE SOFTWARE DEFAULT FACTORS. |
| | |