2016-12-05 11:42:34RESIDENTIAL (R3) ALTERATION SIXTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 1- NEW ENERGY CALCULATIONS SUBMITTED (FORM R405-2014):
 A) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 B) CLARIFY WHY THE COOLING SYSTEM IS ONLY 12.8 KBTU/HR,
 SEC. R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) ATTIC INFORMATION ON PAGE 2 OF 4 SPECIFIES A VENT
 RATIO OF 1/300. TYPICALLY, THE VENTILATION RATIO IS
 1/150. IN ORDER TO USE THE 1/300 VENT RATIO, THE
 ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE AS REQUIRED BY
 THE EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL, 5TH
 EDITION (2014). OTHERWISE, REVISE THE VENT RATIO TO
 1/150.
  
 D) THE EPL DISPLAY CARD NEEDS TO BE SIGNED BY THE
 BUILDER. ONLY THE NAME OF THE BUILDER WAS PROVIDED. THE
 SIGNATURE DOESN'T MATCH SIGNATURE SHOWN ON THE PERMIT
 APPLICATION. SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 E) ENGINEER OF RECORD COMPLETING THE ENERGY
 CALCULATIONS TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S WHEN SUBMITTING
 DOCUMENTATION FOR PUBLIC RECORDS.
  
 NOTE:
 LABELS FOR DOORS AND WINDOWS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS ARE
 REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT TAKING
 THE SOFTWARE DEFAULT FACTORS.
  