Plan Review Notes
Plan Review Notes For Permit 16010523
Permit Number 16010523
Review Stop B
Sequence Number 5
Notes
Date Text
2016-11-29 14:36:25RESIDENTIAL (R3) ALTERATION FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT CONTRACTOR WILL SUBMIT REQUIRED INFORMATION
 PRIOR TO INSPECTIONS TO AVOID DELAYS/CONFLICTS.
 REVISION FEES WILL APPLY EACH TIME INFORMATION IS
 RESUBMITTED. CONTRACTOR TO ADVICE IF PROVISO OPTION IS
 PREFERRED AT THIS TIME OR IF RESUBMITTING REQUIRED
 INFORMATION PRIOR TO ISSUING PERMIT.
  
  
 NEW COMMENT BASED ON THE ENERGY CALCULATIONS SUBMITTED:
 1- DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH THE INTERIOR AND
 EXTERIOR INSULATION REQUIREMENTS AS REQUIRED BY ENERGY
 CALCULATIONS SUBMITTED. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 2- ENERGY CALCULATIONS SUBMITTED:
  
 NOTE: KEEP IN MIND THAT ENERGY CALCULATION SUBMITTED
 ARE DONE FOR THE ENTIRE HOUSE. ALL OF THE COMMENTS
 BELOW APPLY TO THE ENTIRE HOUSE.
  
  
 A) REVISE INFORMATION ON TABLE R402A SUBMITTED:
 (1) MASONRY WALLS REQUIRE "INSULATION ON WALL INTERIOR"
 OF R-4 AND "INSULATION ON WALL EXTERIOR" OF R-3. THE
 "INSTALLED VALUES" COLUMN WAS NOT COMPLETED. NEED TO
 COMPLETE THE "INSTALLED VALUES" COLUMN. (NOTE: SEE NOTE
 #4 AT THE BOTTOM OF THIS TABLE). SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 REPEAT COMMENT. NOT ADDRESSED.
  
 (2) THE CEILING INFORMATION WAS NOT COMPLETED ON THE
 "INSTALLED VALUES" COLUMN. NEED TO COMPLETE THE
 "INSTALLED VALUES" COLUMN. SEC. R101.5.1.1.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 (3) THE AIR HANDLER UNIT IS NOT ALLOWED IN THE ATTIC.
 REVISE THE "INSTALLED VALUES" COLUMN AS REQUIRED. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 (4) THE ELECTRIC WATER HEATER EF VALUE SHOWN ON THE
 "INSTALLED VALUES" COLUMN DOESN'T COMPLY WITH THE
 PRESCRIPTIVE REQUIREMENTS. REVISE AS REQUIRED. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
  
 B) REVISE INFORMATION ON TABLE R402B SUBMITTED;
 (1) THE WATER HEATER COMPONENT WAS NOT CHECKED. SEC.
 R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
  
 C) THE HEATING INFORMATION SHOWN ON THE ENERGY
 CALCULATIONS ITEM #13A AND #13B DOESN'T MATCH TABLE
 R402A AND EQUIPMENT INFORMATION SHOWN ON THE MECHANICAL
 PLAN. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.1
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) PERSON DOING THE ENERGY CALCULATIONS NEED TO
 COORDINATE INFORMATION SHOWN ON THE FRONT PAGE OF THE
 ENERGY CALCULATIONS WIT INFORMATION SHOWN ON TABLE
 R402A. SEC. R101.5.1.1.1 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
  
 NOTE: IF UNABLE TO COMPLY WITH THE ABOVE REQUIREMENTS
 USING THE PRESCRIPTIVE FORM R402-2014 SUBMITTED, THEN
 PERFORMANCE METHOD FORM R405-2014 MAY BE USED INSTEAD.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]