| 2016-10-26 16:42:36 | RESIDENTIAL (R3) ALTERATION FOURTH BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED: |
| | A) INFORMATION SUBMITTED IS INCOMPLETE. MISSING TABLES |
| | R402A AND TABLE R402B. AND, BOTH NEED TO BE COMPLETE |
| | BEFORE SUBMITTAL. |
| | |
| | B) REVISE WALL TYPE AND INSULATION SHOWN ON ITEM #9. |
| | NEED TO SPECIFY THE INSULATION ON THE INTERIOR OF THE |
| | MASONRY WALL AND THE INSULATION ON THE EXTERIOR OF THE |
| | MASONRY WALL. NOTE: CALCULATIONS SUBMITTED ARE FOR THE |
| | ENTIRE HOUSE. THIS REQUIREMENTS APPLIES TO ALL EXISTING |
| | EXTERIOR WALLS. NEED TO PROVIDE PROOF THAT EXISTING |
| | WALLS WILL MEET THIS CRITERIA. ALSO, NEED TO SPECIFY |
| | THE INFILL WOOD FRAME WALL INSTALLED TO CLOSE THE |
| | EXISTING GARAGE DOOR OPENING. SEC. R101.5.1.1.1 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | NOTE: IF UNABLE TO COMPLY WITH THE ABOVE REQUIREMENTS |
| | USING THE PRESCRIPTIVE FORM R402-2014 SUBMITTED, THEN |
| | PERFORMANCE METHOD FORM R405-2014 MAY BE USED INSTEAD. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) HORIZONTAL SLIDER WINDOWS THAT MEET THE CALCULATED |
| | DESIGN PRESSURES FOR THE HORIZONTAL SLIDERS IN THE |
| | LIVING ROOM. DRAWINGS SUBMITTED WITH FLORIDA PRODUCT |
| | APPROVAL FL15814-R2 DON'T MEET THE DESIGN PRESSURES |
| | SHOWN ON DRAWING A1. |
| | |
| | B) EXTERIOR DOORS. DRAWINGS SUBMITTED WITH FLORIDA |
| | PRODUCT APPROVAL FL14569 DON'T MEET THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. REPEAT |
| | COMMENT. THREE TIMES. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | NEW COMMENTS: |
| | 4- WINDOWS SHOWN ON DRAWING A1 WERE REVISED. THE |
| | FOLLOWING REVISIONS ARE REQUIRED: |
| | A) WINDOW SIZES FOR BEDROOM #3 DON'T COMPLY WITH THE |
| | EGRESS REQUIREMENTS. CLEARLY SPECIFY SIZE AND TYPE OF |
| | EXISTING WINDOWS TO VERIFY COMPLIANCE WITH THE EGRESS |
| | REQUIREMENTS OF SEC. 704 FBC-EXISTING BUILDING, 5TH |
| | EDITION (2014). |
| | |
| | B) REVISE EXTERIOR ELEVATIONS ON SHEET A2 TO MATCH |
| | REVISED WINDOWS ON SHEET A1. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |