| Notes |
| Date |
Text |
| 2016-06-15 10:14:56 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | PASSED WITH A PROVISO | | | | | | 1) NEC 250.94 BONDING FOR OTHER SYSTEMS. THE | | | INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE | | | INSTALLED. | | | | | | 2) NEC 408.36 A PANELBOARD SHALL BE PROTECTED BY AN | | | OCPD HAVING A RATING NOT GREATER THAN THAT OF THE | | | PANELBOARD. ( SEE RED LINE MARKS ON PLANS ) | | 2016-06-07 11:34:23 | NEW DRAWINGS SUBMITTED. JG. | | | | | | | | | ****NOTE: | | | THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND, | | | THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE | | | PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL | | | DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON | | | PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON | | | THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED | | | AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING | | | DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE | | | NOT ALLOWED. |
|