| 2016-06-06 18:48:42 | RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | ****NOTE: |
| | THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND, |
| | THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE |
| | PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL |
| | DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON |
| | PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON |
| | THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED |
| | AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING |
| | DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE |
| | NOT ALLOWED. |
| | |
| | |
| | ORIGINAL COMMENT: |
| | 1- PROVIDE ENERGY CALCULATIONS. SEC. R101.4.3 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT |
| | COMMENT). |
| | RESPONSE: REPEAT COMMENT (3 TIMES). NOT ADDRESSED. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | ORIGINAL COMMENT: |
| | A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA |
| | PRODUCT APPROVAL FL15699-R2 DON'T MATCH. DRAWINGS |
| | SUBMITTED ARE FOR THE SH 3700 SERIES WINDOWS, WHILE |
| | FLORIDA PRODUCT APPROVAL FL15699-R2 IS FOR THE SH 3100 |
| | SERIES WINDOWS. PROVIDE PRODUCT APPROVAL AND DRAWINGS |
| | THAT MATCH. |
| | RESPONSE: FLORIDA PRODUCT APPROVAL FL13406-R1 SUBMITTED |
| | NOW IS FOR HORIZONTAL SLIDER WINDOWS. THERE ARE NO |
| | HORIZONTAL SLIDER WINDOWS SPECIFIED ON PLANS. THIS |
| | FLORIDA PRODUCT APPROVAL IS FOR THE 2010 CODE VERSION. |
| | NEED PRODUCT APPROVAL FOR THE CURRENT 2014 CODE |
| | VERSION. THIS PRODUCT APPROVAL IS FOR NON-IMPACT |
| | WINDOWS (NON-IMPACT WINDOWS REQUIRE HURRICANE |
| | SHUTTERS). PROVIDE PRODUCT APPROVAL FOR THE WINDOW THAT |
| | IS SPECIFIED ON PLANS. |
| | |
| | NEW COMMENT: |
| | B) HURRICANE SHUTTERS IF THE WINDOWS AND DOORS DON'T |
| | HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE CITY SAMPLE. PLEASE, CONTACT ME TO GUIDE |
| | YOU HOW TO GET THE CITY SAMPLE. |
| | |
| | ORIGINAL COMMENT: |
| | C) EXTERIOR DOORS. DRAWINGS SUBMITTED WITH FLORIDA |
| | PRODUCT APPROVAL FL13540-R3 DON'T MEET THE DESIGN |
| | PRESSURES CALCULATED BY THE ENGINEER OF RECORD. ALSO, |
| | THE DRAWINGS ARE NOT LEGIBLE. PROVIDE PRODUCT APPROVAL |
| | THAT MEETS THE CALCULATED DESIGN PRESSURES AND PROVIDE |
| | LEGIBLE COPIES. |
| | RESPONSE: DOORS SUBMITTED WITH FLORIDA PRODUCT APPROVAL |
| | FL13540 DON'T MEET THE CALCULATED DESIGN PRESSURES. |
| | REPEAT COMMENT. NEED DOOR THAT MEETS THE CALCULATED |
| | DESIGN PRESSURES. |
| | |
| | ORIGINAL COMMENT: |
| | D) WINDOW MULLIONS: |
| | (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS |
| | FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL |
| | FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014. |
| | (REPEAT COMMENT). |
| | (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). (REPEAT COMMENT). |
| | RESPONSE: COMMENTS NOT ADDRESSED AT ALL. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS |
| | FOR REFERENCE. |
| | |