Plan Review Notes
Plan Review Notes For Permit 16010523
Permit Number 16010523
Review Stop B
Sequence Number 3
Notes
Date Text
2016-06-06 18:48:42RESIDENTIAL (R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW CHECKLIST.
 CODE: FBC-5TH EDITION (2014).
  
 ****NOTE:
 THE ADDRESS OF THE JOB WAS CHANGED WITH WITHE-OUT. AND,
 THE NAME OF THE OWNER DOESN'T MATCH OWNER LISTED ON THE
 PROPERTY APPRAISER OR CITY RECORDS. PROVIDE LEGAL
 DOCUMENTS SHOWING PROOF OF THE CURRENT OWNER SHOWN ON
 PLANS. ANY CHANGES DONE TO THE PLANS NEED TO BE DONE ON
 THE ORIGINAL DRAWINGS, AND, DRAWINGS TO BE RE-SIGNED
 AND RE-SEALED BY THE ENGINEER OF RECORD WHEN SUBMITTING
 DOCUMENTS FOR PUBLIC RECORDS. ALTERATIONS BY HAND ARE
 NOT ALLOWED.
  
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS. SEC. R101.4.3 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT).
 RESPONSE: REPEAT COMMENT (3 TIMES). NOT ADDRESSED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 ORIGINAL COMMENT:
 A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL15699-R2 DON'T MATCH. DRAWINGS
 SUBMITTED ARE FOR THE SH 3700 SERIES WINDOWS, WHILE
 FLORIDA PRODUCT APPROVAL FL15699-R2 IS FOR THE SH 3100
 SERIES WINDOWS. PROVIDE PRODUCT APPROVAL AND DRAWINGS
 THAT MATCH.
 RESPONSE: FLORIDA PRODUCT APPROVAL FL13406-R1 SUBMITTED
 NOW IS FOR HORIZONTAL SLIDER WINDOWS. THERE ARE NO
 HORIZONTAL SLIDER WINDOWS SPECIFIED ON PLANS. THIS
 FLORIDA PRODUCT APPROVAL IS FOR THE 2010 CODE VERSION.
 NEED PRODUCT APPROVAL FOR THE CURRENT 2014 CODE
 VERSION. THIS PRODUCT APPROVAL IS FOR NON-IMPACT
 WINDOWS (NON-IMPACT WINDOWS REQUIRE HURRICANE
 SHUTTERS). PROVIDE PRODUCT APPROVAL FOR THE WINDOW THAT
 IS SPECIFIED ON PLANS.
  
 NEW COMMENT:
 B) HURRICANE SHUTTERS IF THE WINDOWS AND DOORS DON'T
 HAVE IMPACT GLASS. AND, PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE. PLEASE, CONTACT ME TO GUIDE
 YOU HOW TO GET THE CITY SAMPLE.
  
 ORIGINAL COMMENT:
 C) EXTERIOR DOORS. DRAWINGS SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL13540-R3 DON'T MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD. ALSO,
 THE DRAWINGS ARE NOT LEGIBLE. PROVIDE PRODUCT APPROVAL
 THAT MEETS THE CALCULATED DESIGN PRESSURES AND PROVIDE
 LEGIBLE COPIES.
 RESPONSE: DOORS SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL13540 DON'T MEET THE CALCULATED DESIGN PRESSURES.
 REPEAT COMMENT. NEED DOOR THAT MEETS THE CALCULATED
 DESIGN PRESSURES.
  
 ORIGINAL COMMENT:
 D) WINDOW MULLIONS:
 (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS
 FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL
 FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014.
 (REPEAT COMMENT).
 (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014). (REPEAT COMMENT).
 RESPONSE: COMMENTS NOT ADDRESSED AT ALL.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  