| 2016-01-26 15:05:22 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. |
| | CODE: FBC-5TH EDITION (2014) |
| | |
| | 1- FLOOR PLAN SUBMITTED SHOWS A LIVING/DEN ROOM ON THE |
| | REAR OF THE HOUSE. ACCORDING TO CITY RECORDS AND THE |
| | PALM BEACH COUNTY PROPERTY APPRAISER THIS ROOM IS AN |
| | ENCLOSED PORCH NOT LIVABLE AREA. BRING PLANS TO PALM |
| | BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT FEES |
| | ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF |
| | PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE |
| | ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS FOR THE AREA CONVERTED |
| | FROM PORCH TO LIVABLE SPACE. SEC. R101.4.3 OF |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | NOTE: COORDINATE ENERGY CALCULATIONS INFORMATION WITH |
| | INFORMATION SHOWN ON THE INFORMATION REQUESTED ON ITEM |
| | #2 ABOVE. |
| | |
| | 3- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED |
| | BY SEC. R315 OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 4- SPECIFY SIZE AND TYPE OF EXISTING WINDOWS (SPECIALLY |
| | THE BEDROOM WINDOWS) TO VERIFY COMPLIANCE WITH THE |
| | EGRESS REQUIREMENTS OF SEC. 704 OF FBC-EXISTING |
| | BUILDING, 5TH EDITION (2014). |
| | |
| | 5- ACCORDING TO SEC. R301.2.1.4 OF FBC-RESIDENTIAL, |
| | THIS BUILDING IS LOCATED IN EXPOSURE "C". DESIGN |
| | PRESSURES SPECIFIED FOR THE DOORS AND WINDOWS ARE FOR |
| | EXPOSURE "B". REVISE THE DESIGN PRESSURES TO CORRESPOND |
| | TO EXPOSURE "C". |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA |
| | PRODUCT APPROVAL FL14604-R3 DON'T MATCH DRAWINGS |
| | SUBMITTED WITH FL14604-R3 FOR THE 2014 CODE VERSION. |
| | RE-SUBMIT COMPLETE PACKAGE THAT MATCHES. ALSO FLORIDA |
| | PRODUCT APPROVAL FL14604-R3 DOESN'T MATCH FLORIDA |
| | PRODUCT APPROVAL LISTED ON THE WINDOW/DOOR SCHEDULE |
| | SUBMITTED. REVISE AS REQUIRED. |
| | |
| | B) EXTERIOR DOORS. FLORIDA PRODUCT APPROVAL FL15558-R0 |
| | SUBMITTED IS FOR 2010 CODE VERSION. NEED TO PROVIDE |
| | PRODUCT APPROVAL FOR THE CURRENT CODE VERSION. THE |
| | CURRENT CODE IS 2014. ALSO, REVISE THE WINDOW/DOOR |
| | SCHEDULE ACCORDINGLY. |
| | |
| | C) WINDOW MULLIONS: |
| | (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS |
| | FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL |
| | FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014. |
| | ALSO, REVISE THE WINDOW/DOOR SCHEDULE ACCORDINGLY. |
| | |
| | (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 7- ALL DRAWINGS SUBMITTED NEED TO HAVE THE NAME AND |
| | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS |
| | REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |