2016-01-26 15:05:22RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014)
  
 1- FLOOR PLAN SUBMITTED SHOWS A LIVING/DEN ROOM ON THE
 REAR OF THE HOUSE. ACCORDING TO CITY RECORDS AND THE
 PALM BEACH COUNTY PROPERTY APPRAISER THIS ROOM IS AN
 ENCLOSED PORCH NOT LIVABLE AREA. BRING PLANS TO PALM
 BEACH COUNTY (2300 N. JOG RD.) FOR IMPACT FEES
 ASSESSMENT. BRING BACK COUNTY STAMPED PLANS AND COPY OF
 PAID RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE
 ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- PROVIDE ENERGY CALCULATIONS FOR THE AREA CONVERTED
 FROM PORCH TO LIVABLE SPACE. SEC. R101.4.3 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE ENERGY CALCULATIONS INFORMATION WITH
 INFORMATION SHOWN ON THE INFORMATION REQUESTED ON ITEM
 #2 ABOVE.
  
 3- SPECIFY ON PLANS CARBON MONOXIDE ALARMS AS REQUIRED
 BY SEC. R315 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- SPECIFY SIZE AND TYPE OF EXISTING WINDOWS (SPECIALLY
 THE BEDROOM WINDOWS) TO VERIFY COMPLIANCE WITH THE
 EGRESS REQUIREMENTS OF SEC. 704 OF FBC-EXISTING
 BUILDING, 5TH EDITION (2014).
  
 5- ACCORDING TO SEC. R301.2.1.4 OF FBC-RESIDENTIAL,
 THIS BUILDING IS LOCATED IN EXPOSURE "C". DESIGN
 PRESSURES SPECIFIED FOR THE DOORS AND WINDOWS ARE FOR
 EXPOSURE "B". REVISE THE DESIGN PRESSURES TO CORRESPOND
 TO EXPOSURE "C".
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) SINGLE HUNG WINDOWS. DRAWINGS SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL14604-R3 DON'T MATCH DRAWINGS
 SUBMITTED WITH FL14604-R3 FOR THE 2014 CODE VERSION.
 RE-SUBMIT COMPLETE PACKAGE THAT MATCHES. ALSO FLORIDA
 PRODUCT APPROVAL FL14604-R3 DOESN'T MATCH FLORIDA
 PRODUCT APPROVAL LISTED ON THE WINDOW/DOOR SCHEDULE
 SUBMITTED. REVISE AS REQUIRED.
  
 B) EXTERIOR DOORS. FLORIDA PRODUCT APPROVAL FL15558-R0
 SUBMITTED IS FOR 2010 CODE VERSION. NEED TO PROVIDE
 PRODUCT APPROVAL FOR THE CURRENT CODE VERSION. THE
 CURRENT CODE IS 2014. ALSO, REVISE THE WINDOW/DOOR
 SCHEDULE ACCORDINGLY.
  
 C) WINDOW MULLIONS:
 (1) FLORIDA PRODUCT APPROVAL FL 16051-R0 SUBMITTED IS
 FOR 2010 CODE VERSION. NEED TO PROVIDE PRODUCT APPROVAL
 FOR THE CURRENT CODE VERSION. THE CURRENT CODE IS 2014.
 ALSO, REVISE THE WINDOW/DOOR SCHEDULE ACCORDINGLY.
  
 (2) SPECIFY SIZE OF MULLIONS TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 7- ALL DRAWINGS SUBMITTED NEED TO HAVE THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AS
 REQUIRED BY SEC. 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]