Plan Review Notes
Plan Review Notes For Permit 16010522
Permit Number 16010522
Review Stop P
Sequence Number 3
Notes
Date Text
2017-02-22 11:10:533RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN
 COMPLIED WITH 3RD REQUEST
  
  
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FILTER
 TANKS, TYPE OF FILTER,FILTRATION RATE, PUMPS,CHLORINE
 FEEDER, ETC. 2014 AMEND.SEC. 107.2.1.
  
 2ND REQUEST
 1. SHT WF 201-300-301-301.1 SHOW 11/2" WATER SUPPLY
 LINE SHT WF 101-C-500 SHOW A 1" WATER SUPPLY LINE
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2.SHT WF 200-201-201 HAVE OPPOSING DIRECTION ARROWS IT
 SHOW STWO DIFFERENT ARROWS THE SMALLER HOLLOW ARROWS
 SEEM TO BE WRONG PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 3. SHT WF 500 DETAIL 5 SHOWS A 3" TANK DRAIN THAT DOES
 NOT SHOW UP ON ANY OTHER DRAWINGS PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 NEW COMMENT:
  
 1. SHT. 403 WF 201 THE FOUNTAIN-SHOWN ON THE RIGHT HAS
 A FITTING LABELED AS #1 SANITARY SEWER THE FOUNTAIN ON
 THE LEFT HAS THE SAME LABELED AS #4 FILTER RETURN
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
  
  
  