| Plan Review Notes For Permit 16010522 |
| Permit Number |
16010522 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-02-22 11:10:53 | 3RD REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN | | | COMPLIED WITH 3RD REQUEST | | | | | | | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FILTER | | | TANKS, TYPE OF FILTER,FILTRATION RATE, PUMPS,CHLORINE | | | FEEDER, ETC. 2014 AMEND.SEC. 107.2.1. | | | | | | 2ND REQUEST | | | 1. SHT WF 201-300-301-301.1 SHOW 11/2" WATER SUPPLY | | | LINE SHT WF 101-C-500 SHOW A 1" WATER SUPPLY LINE | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2.SHT WF 200-201-201 HAVE OPPOSING DIRECTION ARROWS IT | | | SHOW STWO DIFFERENT ARROWS THE SMALLER HOLLOW ARROWS | | | SEEM TO BE WRONG PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 3. SHT WF 500 DETAIL 5 SHOWS A 3" TANK DRAIN THAT DOES | | | NOT SHOW UP ON ANY OTHER DRAWINGS PLEASE CLARIFY. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | NEW COMMENT: | | | | | | 1. SHT. 403 WF 201 THE FOUNTAIN-SHOWN ON THE RIGHT HAS | | | A FITTING LABELED AS #1 SANITARY SEWER THE FOUNTAIN ON | | | THE LEFT HAS THE SAME LABELED AS #4 FILTER RETURN | | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | | | | | | | | | |
|