| 2016-12-20 10:17:37 | 2ND REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN |
| | COMPLIED WITH |
| | |
| | 1) SHT. WF-100 & WF-200 SHOWS THE DISCHARGE FROM THE |
| | FOUNTAIN DISCHARGING TO THE SANITARY SEWER SYSTEM. THE |
| | DISCHARGE FROM THE FOUNTAINS CANNOT DISCHARGE TO THE |
| | SANITARY OR STORM SYSTEM PER CITY OF WPB CODE OF |
| | ORDINANCES SEC. 90-126 & 90-203. ALSO REFER TO THE |
| | OVERFLOW DRAINS. |
| | 2) CLEARLY EXPLAIN THE TYPE OF WASTE THAT WILL BE |
| | DISCHARGED INTO THE SANITARY SYSTEM FROM THE VAULT |
| | SUMP. WILL THERE BE ANY CHANCES OF CHLORINE BEING |
| | DISCHARGED TO THE SANITARY SYSTEM? CLARIFY. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FILTER |
| | TANKS, TYPE OF FILTER,FILTRATION RATE, PUMPS,CHLORINE |
| | FEEDER, ETC. 2014 AMEND.SEC. 107.2.1. |
| | 4) SHT. WF-201 - EXPLAIN THE SEQUENCE OF OPERATION FOR |
| | THE OVERFLOW DRAIN AS SHOWN ON THE SCHEMATIC - I AM |
| | CONFUSED BY THE LOCATION OF THE FLOW ARROWS.THE |
| | OVERFLOW APPEARS TO DRAIN INTO A 3" LINE THAT HAS A 3" |
| | CONNECTION TO THE SANITARY SEWER AND ALSO A 3" DRAIN |
| | VALVE, CONTINUING TO THE PROSTRAINER AND PUMP AND BACK |
| | TO THE FOUNTAIN. THERE ARE ALSO 2" LINES COMING FROM |
| | THE FILTER TANK THAT APPEAR TO CONNECT TO THE 3" |
| | OVERFLOW DRAIN, CREATING OPPOSING FLOWS TO THE 3" |
| | DRAIN. CLARIFY. |
| | 5) SHT. C5.00 - SHOWS A 2 INCH FOUNTAIN VAULT FORCE |
| | MAIN. THIS LINE IS NOT SHOWN ON SHT. WF-201. HYDRAULIC |
| | SCHEMATIC. CLARIFY. |
| | |
| | NEW COMMENTS: |
| | 1. SHT WF 201-300-301-301.1 SHOW 11/2" WATER SUPPLY |
| | LINE SHT WF 101-200-202 SHOW A 1" WATER SUPPLY LINE |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2.SHT WF 200-201-201 HAVE OPPOSING DIRECTION ARROWS IT |
| | SHOW STWO DIFFERENT ARROWS THE SMALLER HOLLOW ARROWS |
| | SEEM TO BE WRONG PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 3. SHT WF 500 DETAIL 5 SHOWS A 3" TANK DRAIN THAT DOES |
| | NOT SHOW UP ON ANY OTHER DRAWINGS PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | |
| | |