Plan Review Notes
Plan Review Notes For Permit 16010522
Permit Number 16010522
Review Stop P
Sequence Number 1
Notes
Date Text
2016-02-06 07:24:411) SHT. WF-100 & WF-200 SHOWS THE DISCHARGE FROM THE
 FOUNTAIN DISCHARGING TO THE SANITARY SEWER SYSTEM. THE
 DISCHARGE FROM THE FOUNTAINS CANNOT DISCHARGE TO THE
 SANITARY OR STORM SYSTEM PER CITY OF WPB CODE OF
 ORDINANCES SEC. 90-126 & 90-203. ALSO REFER TO THE
 OVERFLOW DRAINS.
 2) CLEARLY EXPLAIN THE TYPE OF WASTE THAT WILL BE
 DISCHARGED INTO THE SANITARY SYSTEM FROM THE VAULT
 SUMP. WILL THERE BE ANY CHANCES OF CHLORINE BEING
 DISCHARGED TO THE SANITARY SYSTEM? CLARIFY.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FILTER
 TANKS, TYPE OF FILTER,FILTRATION RATE, PUMPS,CHLORINE
 FEEDER, ETC. 2014 AMEND.SEC. 107.2.1.
 4) SHT. WF-201 - EXPLAIN THE SEQUENCE OF OPERATION FOR
 THE OVERFLOW DRAIN AS SHOWN ON THE SCHMATIC - I AM
 CONFUSED BY THE LOCATION OF THE FLOW ARROWS.THE
 OVERFLOW APPEARS TO DRAIN INTO A 3" LINE THAT HAS A 3"
 CONNECTION TO THE SANITARY SEWER AND ALSO A 3" DRAIN
 VALVE, CONTINUING TO THE PROSTRAINER AND PUMP AND BACK
 TO THE FOUNTAIN. THERE ARE ALSO 2" LINES COMING FROM
 THE FILTER TANK THAT APPEAR TO CONNECT TO THE 3"
 OVERFLOW DRAIN, CREATING OPPOSING FLOWS TO THE 3"
 DRAIN. CLARIFY.
 5) SHT. C5.00 - SHOWS A 2 INCH FOUNTAIN VAULT FORCE
 MAIN. THIS LINE IS NOT SHOWN ON SHT. WF-201. HYDRAULIC
 SCHEMATIC. CLARIFY.
  
  