| Plan Review Notes For Permit 16010522 |
| Permit Number |
16010522 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-06 07:24:41 | 1) SHT. WF-100 & WF-200 SHOWS THE DISCHARGE FROM THE | | | FOUNTAIN DISCHARGING TO THE SANITARY SEWER SYSTEM. THE | | | DISCHARGE FROM THE FOUNTAINS CANNOT DISCHARGE TO THE | | | SANITARY OR STORM SYSTEM PER CITY OF WPB CODE OF | | | ORDINANCES SEC. 90-126 & 90-203. ALSO REFER TO THE | | | OVERFLOW DRAINS. | | | 2) CLEARLY EXPLAIN THE TYPE OF WASTE THAT WILL BE | | | DISCHARGED INTO THE SANITARY SYSTEM FROM THE VAULT | | | SUMP. WILL THERE BE ANY CHANCES OF CHLORINE BEING | | | DISCHARGED TO THE SANITARY SYSTEM? CLARIFY. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FILTER | | | TANKS, TYPE OF FILTER,FILTRATION RATE, PUMPS,CHLORINE | | | FEEDER, ETC. 2014 AMEND.SEC. 107.2.1. | | | 4) SHT. WF-201 - EXPLAIN THE SEQUENCE OF OPERATION FOR | | | THE OVERFLOW DRAIN AS SHOWN ON THE SCHMATIC - I AM | | | CONFUSED BY THE LOCATION OF THE FLOW ARROWS.THE | | | OVERFLOW APPEARS TO DRAIN INTO A 3" LINE THAT HAS A 3" | | | CONNECTION TO THE SANITARY SEWER AND ALSO A 3" DRAIN | | | VALVE, CONTINUING TO THE PROSTRAINER AND PUMP AND BACK | | | TO THE FOUNTAIN. THERE ARE ALSO 2" LINES COMING FROM | | | THE FILTER TANK THAT APPEAR TO CONNECT TO THE 3" | | | OVERFLOW DRAIN, CREATING OPPOSING FLOWS TO THE 3" | | | DRAIN. CLARIFY. | | | 5) SHT. C5.00 - SHOWS A 2 INCH FOUNTAIN VAULT FORCE | | | MAIN. THIS LINE IS NOT SHOWN ON SHT. WF-201. HYDRAULIC | | | SCHEMATIC. CLARIFY. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|