Plan Review Notes
Plan Review Notes For Permit 16010520
Permit Number 16010520
Review Stop Z
Sequence Number 2
Notes
Date Text
2016-07-22 12:02:18FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE SITE LAYOUT SHOWN ON THE PLANS IS DIFFERENT FROM
 THE APPROVED PLANS. THE PROPOSED SITE LAYOUT IS
 TENTATIVELY SCHEDULED TO BE HEARD BY THE CITY
 COMMISSION ON AUGUST 29, 2016. ZONING CANNOT GIVE FINAL
 APPROVAL OF THE PERMIT UNTIL AFTER THE COMMISSION
 APPROVAL.
  
 2) REPEAT COMMENT: THERE CONTINUE TO BE LIGHTS SHOWN ON
 THE ELECTRICAL SITE PLAN THAT ARE NOT LISTED ON THE
 ELECTRICAL SCHEDUL, EX. - ALL OF THE FX SERIES OF
 LIGHTS.
  
 3) REPEAT COMMENT: LIGHTS MAY NOT BE MOUNTED IN THE
 TREES. THE ELECTRICAL SCHEDULE LISTS TREE TYPES F10 AND
 F10A AS TREE MOUNTED.
  
 4) REPEAT COMMENT: NO PHOTOMETRIC PLAN WAS PROVIDED.
  
 5) THE ELECTRICAL SITE PLAN SHOWS AN F11 LIGHT TYPE
 THAT IS NOT LISTED ON THE ELECTRICAL SCHEDULE. IS THIS
 SUPPOSED TO BE THE FS2 BOLLARD LIGHT?
  
 6) HOW TALL ARE THE BOLLARD LIGHTS?
  
 7) WHAT DOES THE WR TYPE OF LIGHT LOOK LIKE? IT IS NOT
 SHOWN ON SHEET LGT 251.1. DOES ANY PART OF THE WR LIGHT
 EXTEND ABOVE THE WALL?
  
 8) PROVIDE DETAILS, TO INCLUDE POLE HEIGHT, FOR THE
 FS21 TYPE LIGHT.
  
 9) THE ELECTRICAL SITE PLAN SHOWS THE POLE PLUS FIXTURE
 FOR TYPE FS1 AT 16 FEET IN HEIGHT. THE ELECTRICAL
 SCHEDULE LISTS TYPE FS1 AS HAVING A 10 FOOT POLE WITH A
 12 OVERALL HEIGHT. ALL PLANS SHALL SHOW SAME
 CONDITIONS. PLEASE NOTE THAT THE 12 FOOT HEIGHT WORKS
 BETTER WITH THE SPECIFIC TREES AND THEIR LOCATIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  