| 2017-03-03 07:19:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | COMMENTS FROM PREVIOUS REVIEW: | | | | | | 1. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED LIGHT | | | POLES, FBC 1609. INCLUDE WIND DESIGN CRITERIA. | | | | | | 2. PROVIDE CALCS FOR THE LIGHT POLES AND FIXTURES, FBC | | | 1609. | | | | | | IT IS NOT CLEAR HOW THESE ITEMS WERE ADDRESSED. A | | | RESPONSE LETTER WAS NOT PROVIDED, AND IT DOES NOT | | | APPEAR THAT THIS INFORMATION WAS ADDED TO THE PLAN. IF | | | YOU FEEL THAT THIS INFORMATION IS INCLUDED IN THE | | | SUBMITTAL, PLEASE ADVISE AS TO FILE NAMES. A DETAIL ON | | | AN ELECTRICAL SHEET WAS PROVIDED BUT IS NOT A COMPLETE | | | STRUCTURAL DETAIL. | | | | | | S003 INCLUDES WIND DESIGN CRITERIA, BUT I WAS NOT ABLE | | | TO LOCATE AN S SHEET WITH THE STRUCTURAL DETAIL FOR THE | | | LIGHT POLES, AND WAS NOT ABLE TO LOCATE THE | | | CALCULATIONS FOR THE POLES AND FIXTURES. THIS | | | INFORMATION IS OFTEN PROVIDED BY THE SPECIALTY | | | ENGINEER. IF PROVIDED BY A SPECIALTY ENGINEER, HAVE THE | | | DELEGATED ENGINEERING REVIEWED BY DOR PRIOR TO | | | SUBMITTAL. | | | |
|