| 2016-01-26 18:12:13 | FAILED | | | | | | 1) THE SITE, LANDSCAPE AND CIVIL PLANS SHOW EIGHT LIGHT | | | POLES AROUND THE PARKING LOT. THE ELECTRICAL SITE PLAN | | | SHOWS 19 POLES (FS1) AROUND THE PARKING LOT, TO INCLUDE | | | ONE IN THE DRAIN FLUE. THE 19 POLES SEEM EXCESSIVE. | | | | | | 2) THE POLE SHOWN ON SHEET E050 IS LABELED AS F51, YET | | | THIS DOES NOT EXIST ON THE PLAN. | | | | | | 3) LIGHTS MAY NOT BE MOUNTED IN THE TREES. | | | | | | 4) NO PHOTOMETRIC PLAN WAS PROVIDED. | | | | | | 5) WHERE ARE THE DETAILS FOR THE BOLLARD LIGHTS AND THE | | | WALL PACKS. | | | | | | 6) WHAT ARE THE WP, WR AND LA SERIES OF LIGHTS AND WHAT | | | DO THEY LOOK LIKE? | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|