2016-01-26 18:12:13FAILED
  
 1) THE SITE, LANDSCAPE AND CIVIL PLANS SHOW EIGHT LIGHT
 POLES AROUND THE PARKING LOT. THE ELECTRICAL SITE PLAN
 SHOWS 19 POLES (FS1) AROUND THE PARKING LOT, TO INCLUDE
 ONE IN THE DRAIN FLUE. THE 19 POLES SEEM EXCESSIVE.
  
 2) THE POLE SHOWN ON SHEET E050 IS LABELED AS F51, YET
 THIS DOES NOT EXIST ON THE PLAN.
  
 3) LIGHTS MAY NOT BE MOUNTED IN THE TREES.
  
 4) NO PHOTOMETRIC PLAN WAS PROVIDED.
  
 5) WHERE ARE THE DETAILS FOR THE BOLLARD LIGHTS AND THE
 WALL PACKS.
  
 6) WHAT ARE THE WP, WR AND LA SERIES OF LIGHTS AND WHAT
 DO THEY LOOK LIKE?
  