2016-03-29 13:13:31INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE ADDRESS ZONING COMMENTS FOR A COMPLETE
 ELECTRICAL REVIEW.
 2. PLEASE PROVIDE ENGINEERED POLE DETAILS TO WITHSTAND
 WIND LOADS FOR AREA OF INSTALLATION
 3. BUILDING REVIEW WILL BE REQUIRED FOR THE STRUCTURAL
 CONCRETE POLE BASE DESIGN.
 4. COULD NOT LOCATE PHOTOMETRICS UNDER ORIGINAL
 SUBMITTAL PLEASE CLARIFY.
 5. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER LISTED BELOW SHOULD
 YOU HAVE ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  