| Plan Review Notes For Permit 16010504 |
| Permit Number |
16010504 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-02-04 09:41:59 | APPROIVED THE APPLICATION BUT MADE A NOTE FOR THE | | | INSPECTOR: NOTICE TO INSPECTOR: | | | VERIFY SERVICE CONDUCTOR SIZING AS #2 AWG IS ONLY RATED | | | FOR 115 AMP AND APPEARS TO BE PROTECTED WITH BY 150 AMP | | | OCPD. WORK PERMITTED UNDER PERMIT 14020436. | | | |
|