| Plan Review Notes For Permit 16010501 |
| Permit Number |
16010501 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-03-07 12:36:16 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL | | | | | | FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW | | | SUPPLY DUCTS PER FBC-R M16; PROVIDE AN ENERGY | | | SUBMITTAL. | | | | | | FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 | | | SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO | | | DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. | | | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | | COMPLIANCE BY SECTION 405. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|