| Plan Review Notes For Permit 16010495 |
| Permit Number |
16010495 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-05 07:27:00 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010495 | | | 2/5/16 | | | | | | 1) INDICATE ON THE PLAN IF THERE IS AN EXISTING DUCT | | | SMOKE DETECTOR FOR RTU-1, AND SEE SECTION 606.2.1- IF | | | THE UNIT HAS A DESIGN CAPACITY GREATER THAN 2000 CFM, A | | | DUCT SMOKE DETECTOR IS REQUIRED IN THE RETURN AIR | | | SYSTEM. | | | 2) IF ANY PLANS ARE TO BE REVISED, AS A COURTESY, | | | PLEASE PLACE A NOTE INDICATING THE OVEN EXHAUST AND | | | FIRE SUPPRESSION SYSTEM WILL BE DONE UNDER A SEPARATE | | | PERMIT | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|