Plan Review Notes
Plan Review Notes For Permit 16010493
Permit Number 16010493
Review Stop P
Sequence Number 1
Notes
Date Text
2016-01-24 04:41:011)SUBMIT A SITE PLAN SHOWING HOW WATER AND SEWER
 SERVICE WILL BE PROVIDED TO THE MODULAR STRUCTURE.WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) IF THE STRUCTURE WILL DISCHARGE TO A SEWAGE TANK,
 SHOW THE LOCATION ON THE SITE PLAN AND INDICATE THE
 CAPACITY OF THE TANK. TANKS EXCEEDING 300 GALLONS
 REQUIRE A PERMIT FROM THE PALM BEACH COUNTY HEALTH
 DEPT.
 3) THE WATER SERVICE TO THE STRUCTURE SHALL BE
 PROTECTED BY A BACKFLOW PREVENTION DEVICE. THE DEVICE
 SHALL BE LEAD FREE. SUBMIT TWO COPIES OF THE
 MANUFACTURER'S SPECIFICATIONS FOR THE BACKFLOW
 PREVENTION DEVICE.WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW