| 2016-01-26 13:00:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1. PER NFPA 241- STANDARD FOR SAFEGUARDING |
| | CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, |
| | SECTION 4.2 TEMPORARY OFFICES AND SHEDS SHALL BE |
| | SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN |
| | ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | |
| | 2. PROVIDE A SITE PLAN, INCLUDING ALL DIMENSIONS TO |
| | PROPOERTY LINES AND EXISTING AND PROPOSED BUILDINGS |
| | THAT COMPLY WITH NFPA 241 AS NOTED ABOVE. |
| | |
| | 3. PROVIDE A STATEMENT INDICATING THE INSTALLATION OF A |
| | FIRE SPRINKLER SYSTEM UNDER SEPARATE SHOP DRAWINGS IF |
| | APPLICABLE FOR THE 75 PERCENT REDUCTION NOTED ABOVE. |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |