Plan Review Notes
Plan Review Notes For Permit 16010493
Permit Number 16010493
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-01-26 13:00:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PER NFPA 241- STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2 TEMPORARY OFFICES AND SHEDS SHALL BE
 SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN
 ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 2. PROVIDE A SITE PLAN, INCLUDING ALL DIMENSIONS TO
 PROPOERTY LINES AND EXISTING AND PROPOSED BUILDINGS
 THAT COMPLY WITH NFPA 241 AS NOTED ABOVE.
  
 3. PROVIDE A STATEMENT INDICATING THE INSTALLATION OF A
 FIRE SPRINKLER SYSTEM UNDER SEPARATE SHOP DRAWINGS IF
 APPLICABLE FOR THE 75 PERCENT REDUCTION NOTED ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  