2016-01-22 12:56:58ELECTRICAL PROVISO TO PERMIT 16010486
  
 1. NEC 314.27(A) BOXES USED AT LUMINAIRE OR LAMPHOLDER
 OUTLETS IN A CEILING SHALL BE REQUIRED TO SUPPORT A
 LUMINAIRE WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE
 NOTES ON CEILING BOXES ON PAGE.
 2. NEC 314.27(D) BOXES USED FOR THE SOLE SUPPORT OF
 CEILING FANS SHALL BE MARKED BY THE MANUFACTURER AS
 SUITABLE FOR THE PURPOSE, AND INDICATE THE WEIGHT
 LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT PADDLE
 FANS HEAVIER THAN 70 LBS.
 3. NEC 404.4. WHERE SWITCHES CONTROLLING LIGHTING LOADS
 SUPPLIED BY A GROUNDED BRANCH CIRCUIT, THE GROUNDED
 BRANCH CIRCUIT CONDUCTOR FOR THE CONTROLLED LIGHTING
 CIRCUIT SHALL BE PROVIDED AT THE SWITCH.
  