| Plan Review Notes For Permit 16010471 |
| Permit Number |
16010471 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-21 07:33:18 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010471 | | | 01/21/16 | | | | | | 1) AC PLANS: A) PLACE A NORTH DIRECTIONAL ARROW ON THE | | | PLAN FOR PROPER REVIEW OF THE AC CALCULATIONS. B) | | | PROVIDE THE SUPPLY CFM'S ATR EACH DIFFUSER, AND RETURN | | | CFM'S AT EACH GRILL. C) PROVIDE THE SENSIBLE AND LATENT | | | CAPACITIES OF THE AC SYSTEMS TO VERIFY COMPLIANCE WITH | | | THE CALCULATIONS (EQUIPMENT MAKE AND MODEL SELECTIONS | | | BETWEEN CALCS AND PLAN DO NOT MATCH). | | | 2) PROVIDE AC CALCULATIONS BASED ON THE CORRECT DESIGN | | | TEMPERATURES FOR WEST PALM BEACH- THE DRYBULB | | | TEMPERATURES ON THE SUBMITTED CALCS ARE INCORRECT. | | | 3) PROVIDE DETAILS FOR PRIMARY AND SECONDARY CONDENSATE | | | DISPOSAL. | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE KITCHEN | | | EXHAUST HOOD AND THE APPLIANCE IT IS VENTING. | | | 5) CLARIFY IF THE ELECTRICAL TO POWER THE AC SYSTEMS IS | | | TO BE INCLUDED AS A SUB-PERMIT OF THIS APPLICATION, OR | | | TO BE DONE UNDER A SEPARATE PERMIT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|