| 2016-04-28 09:00:18 | 3RD REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #16010466 |
| | 4/28/16 |
| | |
| | 1) SHEET M-1: THE MODEL NUMBERS FOR THE NEW 3-TON BARD |
| | UNIT SHOWN ON THE PLAN DO NOT MATCH THE NUMBERS SHOWN |
| | ON THE NEW SUBMITTAL- PLEASE CORRECT. |
| | 2) M-1: THE AC SCHEDULE INDICATES 2600 CFM'S OF SUPPLY |
| | AIR FOR THE 3-TON SYSTEM WHICH WOULLD NOT BE POSSIBLE |
| | FOR A 3-TON SYSTYEM. PLEASE NOTE THE NEW BARD SPECS |
| | INDICATE THE UNIT WILL PRODUCE 1100 CFRMS. |
| | 3) THE SUBMITTED PRODUCT APPROVAL FOR THE LOUVER IS |
| | INCOMPLETE: PLEASE PROVIDE A COMPLETE DOCUMENT THAT |
| | INCLUDES THE INSTALLATION INSTRUCTIONS AND |
| | CERTIFICATION CERTIFICATE AS SHOWN ON PAGE-3 OF THE |
| | SUBMITTAL. |
| | 4) PROVIDE AN NOA OR FLORIDA PRODUCT APPROVAL FOR THE |
| | GREENHECK FAN EXTERIOR WEATHERHEAD. |
| | 5) ADVISORY: AS REQUESTED BY THE CONTRACTOR, THE WIND |
| | LOAD ENGINEERING FOR INSTALLATION OF THE BARD UNIT CAN |
| | BE DONE AS A DEFERRED SUBMITTAL. PLEASE REVIEW SECTION |
| | 107.3.4.2 WPB AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE:1) DEFERRED SUBMITTAL: FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |
| | [email protected] |
| | |