| Plan Review Notes For Permit 16010466 |
| Permit Number |
16010466 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-04-04 08:48:17 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010466 | | | 4/4/16 | | | | | | 1) THE ENGINEER OF RECORD JASON LEE P.E. IS REQUIRED TO | | | PROVIDE A RAISED SEAL AND SIGNATURE ON THE SUBMITTED AC | | | LOAD CALCULATIONS IN ACCORDANCE WITH SECTION | | | 61G15023.002 FAC, AND CHAPTER 471 FLORIDA STATUTES. | | | 2) THE SUBMITTED WIND LOAD CALCULATION HAS AN OUTDATED | | | COPIED SEAL AND SIGNATURE. PROVIDE SITE SPECIFIC | | | CALCULATIONS FOR THE NEW AC SYSTEM WITH AN ORIGINAL | | | SEAL AND SIGNATURE FROM THE EOR IN ACCORDANCE WITH | | | FLORIDA STATUTES AND SECTION 61G15023.002 FAC. PLEASE | | | PROVIDE ATTACHMENT DETAILS ON THE PLANS, AND NOTE THAT | | | THE SYSTEM SELECTION SHALL BE BASED ON THE AC LOAD | | | CALCULATIONS BY JASON LEE P.E. WHICH ARE INDICATING A | | | 2-1/2 TON LOAD. | | | 3) THE SUBMITTED VENTILATION CALCULATIONS FROM KIMBERLY | | | HORN MUST BE SIGNED BY THE PERSON WHO PREPARED THE | | | CALCULATIONS- SECTION 107.2.1 WPB AMENDMENTS TO THE | | | FBC-10 BUILDING CODES. | | | 4) AS PREVIOUSLY REQUESTED PROVIDE EQUIPMENT SCHEDULES | | | ON THE PLANS FOR THE AC SYSTEM AND FANS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|