| 2016-04-06 15:44:05 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 1601046 |
| | ADD: 2400 N FLAGLER DR. CURY PARK/ CITY PUMP/ LIFT |
| | STATION ADDITION & RENOVATION |
| | BLDG. RISK CATEGORY: III/ 180 VULT/ MPH |
| | CONT: FLORIDA DESIGN DRILLING CORP. |
| | TEL: 561-844-2966 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. FEB. 03/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. PROPOSED FLOOD ZONE CERTIFICATE. |
| | |
| | 2) 2ND REQUEST. THE DUNKLEBERGER SOILS REPORT SUBMITTED |
| | IS A COPY NOT SIGNED AND SEALED ORIGINALS AS REQUIRED |
| | BY |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 3-5) COMPLIED. |
| | |
| | 6) 2ND REQUEST. PLEASE PROVIDE COMPLIANCE WITH 2014 |
| | FBC-B 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS.NOA 14-1001.05ROLL UP DOOR, NOT |
| | REVIEWD BY THE DESIGNER OF RECORD. |
| | FL14573 NO TECHNICAL SHEETS, NOT REVIEWED BY THE |
| | DESIGNER OF RECORD. |
| | (C) PANEL WALLS: WALL LOUVERS, FL 6876, NO TECHNICAL |
| | SHEETS, NOT REVIEWED BY THE DESIGNER OF RECORD |
| | (D) ROOFING PRODUCTS AND ASSEMBLIESFL5680-R15 NOT |
| | REVIEWED BY THE DESIGNER OF RECORD |
| | |
| | 7) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.4.1 THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 8)COMPLIED. |
| | |
| | 9) PLEASE NOTE REPORT BY DOUGLAS RUGGIANO P. E. WIND |
| | LOADS ANALYSIS AND STRUCTURAL CALCULATIONS FOR |
| | FASTENING REQUIREMENTS OF BARD MANUFACTURING CO. 1 TON |
| | WALL MOUNT UNIT. |
| | DATE STAMPED 12/01/14 ARE COPIES NOT ORIGINALS. NOTE ON |
| | THE FRONT PAGE, SEE PAGE 7 & 8 FOR RESPECTIVE MODEL. |
| | THE PAGES ARE NOT NUMBERED WHAT APPEARS TO BE PAGES 7 & |
| | 8 INDICATE 2.5-3 TON WALL MOUNT UNIT. PAGE 8 INDICATES |
| | THIS DESIGN IS GOOD FOR UP TO 175MPH NOT THE 180MPH AS |
| | INDICATES ON SHEET S-1. |
| | |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS. PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY |
| | THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN |
| | PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX LISTING HOW MANY PAGES ARE |
| | COVERED UNDER THE COVER SHEET OR INDEX SHEET. . |
| | |
| | FL 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL |
| | FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO THE |
| | ENGINEER OF RECORD FOR REVIEW. |
| | |
| | 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |