| Plan Review Notes For Permit 16010466 |
| Permit Number |
16010466 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-25 14:41:59 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | 1. SHEET S 7 - INDICATES A STAIR RAILING OF 39" - NFPA | | | 101, CHAPTER 7, | | | | | | 7.2.2.4.4 HANDRAIL DETAILS; | | | | | | 7.2.2.4.4.1 NEW HANDRAILS ON STAIRS SHALL NOT BE LESS | | | THAN 34 IN. AND NOT MORE THAN 38 IN. ABOVE THE SURFACE | | | OF THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE | | | RAIL FROM THE LEADING EDGE OF THE TREAD. | | | |
|