2016-02-17 09:10:45INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE
 PERMITS FOR THE GENERATOR AND LIGHTNING PROTECTION. FBC
 107.3
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. SHOW THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR
 AT THE SERVICE. NEC 250.66
 4. PLEASE PROVIDE AN INTERSYSTEM BONDING TERMINATION AT
 THE SERVICE ONE-LINE. NEC 250.94. NOTE
 5. CLARIFY THE REDUCTION OF THE NEUTRAL CONDUCTOR AT
 THE SERVICE. NEC 250.61C. PROVIDE A NEUTRAL CALCULATION
 OR CLARIFY.
 6. PROVIDE AIC CALCULATIONS FOR THE NEW SERVICE SHOWN.
 SHOW AVAILABLE FAULT AT THE TRANSFORMER. FBC 107.3
 7. PANEL A AND G NOT SHOWN ON RISER ONE-LINE DIAGRAM.
 LOAD CALCULATIONS NOT SUBMITTED FOR THESE. PLEASE
 PROVIDE, FBC 107.3
 8. STEP DOWN TRANSFORMER (A), SHOW GEC SIZE PER NEC
 250.66. ALSO CLARIFY THE REDUCTION OF THE NEUTRAL
 CONDUCTOR AT THE SECONDARY OUTPUT TO PANEL A. SEE NEC
 250.61C, FBC 107.3
 9. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
  