| Plan Review Notes For Permit 16010466 |
| Permit Number |
16010466 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-02-17 09:10:45 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE PROVIDE A NOTE TO INDICATE REQUIRED SEPARATE | | | PERMITS FOR THE GENERATOR AND LIGHTNING PROTECTION. FBC | | | 107.3 | | | 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, | | | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP | | | AND COMPLETIONS DOCUMENTS. | | | 3. SHOW THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR | | | AT THE SERVICE. NEC 250.66 | | | 4. PLEASE PROVIDE AN INTERSYSTEM BONDING TERMINATION AT | | | THE SERVICE ONE-LINE. NEC 250.94. NOTE | | | 5. CLARIFY THE REDUCTION OF THE NEUTRAL CONDUCTOR AT | | | THE SERVICE. NEC 250.61C. PROVIDE A NEUTRAL CALCULATION | | | OR CLARIFY. | | | 6. PROVIDE AIC CALCULATIONS FOR THE NEW SERVICE SHOWN. | | | SHOW AVAILABLE FAULT AT THE TRANSFORMER. FBC 107.3 | | | 7. PANEL A AND G NOT SHOWN ON RISER ONE-LINE DIAGRAM. | | | LOAD CALCULATIONS NOT SUBMITTED FOR THESE. PLEASE | | | PROVIDE, FBC 107.3 | | | 8. STEP DOWN TRANSFORMER (A), SHOW GEC SIZE PER NEC | | | 250.66. ALSO CLARIFY THE REDUCTION OF THE NEUTRAL | | | CONDUCTOR AT THE SECONDARY OUTPUT TO PANEL A. SEE NEC | | | 250.61C, FBC 107.3 | | | 9. FEEL FREE TO CONTACT ME DIRECTLY SHOULD YOU HAVE ANY | | | QUESTIONS OR CONCERNS. | | | | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | |
|