| Date |
Text |
| 2016-03-23 09:21:27 | SPOKE W/GLEN SPINA OFFICES AND THEY WILL SEND ME AN |
| | EMAIL ACKNOWLEDGING MY REQUIREMENTS. ONCE RECEIVED I |
| | WILL APPROVE THE ELECTRICAL REVIEW WITH A PROVISO |
| | REQUIRING DAYLIGHT ZONE CONTROL IN THESE UNITS. |
| 2016-03-22 14:43:07 | ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN |
| | SATISFACTORILY ADDRESSED, BUT I MAY HAVE OVERSEEN THE |
| | TWO NEW COMMENTS ON THE LIGHTING PAGE AS MENTIONED |
| | BELOW. |
| | |
| | 2ND ELECTRICAL REVIEW NOTES FOR PERMIT #:16010446 |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 |
| | NFPA 70 2011 (NEC) |
| | |
| | CORRECTIONS REQUIRED: |
| | SHEET E2.1 |
| | 1. ROOMS 311, 314 & 318 DO NOT COMPLY WITH THE |
| | FBC-C405.2.2.3 DAYLIGHT ZONE CONTROLS. PLEASE SEPARATE |
| | FIXTURE SWITCHING TO COMPLY. |
| | 2. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING |
| | INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC |
| | RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED & UNCONDITIONED SPACES. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |