| 2016-02-10 16:50:13 | 1ST ELECTRICAL REVIEW NOTES: |
| | REVIEWED FOR COMPLIANCE WITH: |
| | FBC 2010, NEC 2008 |
| | |
| | CORRECTIONS REQUIRED: (ITEMS MARKED IN GREEN ARE ONLY |
| | ENERGY CONSERVATION AND CONVENIENCE SUGGESTIONS) UNIT |
| | DL WAS REVIEWED FIRST, BUT COMMENTS MARKED TYPICAL |
| | APPLY TO ENTIRE PROJECT AND MAY BE REMEDIED WITH A |
| | NOTE. |
| | SHEET E0.1 |
| | 1. CORRECT MISQUOTED FBC SECTIONS AS FOLLOWS: NOTE P: |
| | FBC-EC405.7.3.2 & NOTE Q: FBC-EC405.7.3.1 |
| | SHEET 2.1 |
| | 2. FBC-B1011.1 ADDITIONAL EXIT SIGN REQUIRED WITHIN |
| | THIS AREA AS THERE CAN BE NO MORE THAN 100? BETWEEN |
| | EXIT SIGNS. |
| | 3. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. |
| | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION |
| | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER |
| | CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING |
| | POWER DENSITY CHART TO SHOW COMPLIANCE. |
| | 4. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE. THE |
| | TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING |
| | TO THE APPLICABLE TABLES AS INDICATED IN THIS SECTION. |
| | SHEET E3.1 |
| | 5. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL |
| | EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO |
| | REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED |
| | TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |