2016-02-12 06:32:04INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SHOW ON DRAWING THE RECEPTACLE OUTLETS
 REQUIRED FOR WALL SPACE TO THE LEFT AREA OF THE ROOM.
 COMPLY WITH FBC RES- SEC E39012.1 AND 2.2
 2. PROVIDE A NOTE TO COMPLY WITH AFCI PROTECTION FOR
 BRANCH CIRCUITS AND TAMPER RESISTANT RECEPTACLE PER FBC
 RES- SEC E3902.12 AND E4002.14
 3. SEE FBC RES 314 SMOKE ALARM REQUIREMENTS PER
 ALTERATION. PROVIDE OR SHOW EXISTING SMOKE DETECTORS TO
 COMPLY. SEE EXCEPTION 314.4-3 FOR EASE OF COMPLIANCE.
 4. FURTHER COMMENTS MAT FOLLOW UPON RESUBMITTAL.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  