Plan Review Notes
Plan Review Notes For Permit 16010436
Permit Number 16010436
Review Stop E
Sequence Number 1
Notes
Date Text
2016-02-11 12:44:36INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE REVISE MAIN FUSES SELECTED TO SHOW 60AMP NOT
 40AMP WHICH IS UNDER THE REQUIRED SERVICE SIZE PER NEC
 230.79D
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  