Plan Review Notes
Plan Review Notes For Permit 16010436
Permit Number 16010436
Review Stop B
Sequence Number 1
Notes
Date Text
2016-02-04 11:30:45BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010436
 ADD: 326 FERN ST
 CONT: CB & I ENVIRONMENTAL & INFRASTRUCTURE
 TEL: 813-612-3678
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. FEB. 04/ 2016
 ACTION: DENIED
  
 1) CBI PLANS SHEET # 9 WITH ENCLOSURE PANEL NOTES FOR
 THE WALL SYSTEM FL6231.3 THIS PRODUCT APPROVAL WAS
 UNDER THE 2007 FBC AND NOTE A CURRENT PRODUCT APPROVAL.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31(G) EXTERIOR COOLER, FREEZERS
 2) CBI PLANS SHEET 8 PROVIDES THE WIND DESIGN AS 170
 VULT EXPOSURE B, THE BUILDING RISK CATEGORY I. FOR A
 BUILDING WITH A RISK CATEGORY I THE WIND SPEED IS 160
 VULT, INTERPOLATION BETWEEN THE CONTOUR LINES WILL
 PLACE THE WIND SPEED AT 155. THERE IS A DISCREPANCY
 BETWEEN THE WIND DESIGN SPEED AND THE RISK CATEGORY.
 SEE FBC-B TABLE 1604.5 AND FIGURES FIGURE1609A AND
 FIGURE 1609C.
  
 3) THE SUBMITTED FLORIDA APPROVAL15491.1-R3. 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) PLEASE IDENTIFY BY CIRCLING FOR ENCLOSED STRUCTURES,
 MAXIMUM ALLOWABLE CLEAR SPAN, THE WIND SPEED, EXPOSURE
 LIVE LOADS AND UPLIFT AND DEFLECTION LIMITS AS WELL AS
 THE PANEL THICKNESS GAUGE OF SKIN FOR EVALUATION FOR
 CODE COMPLIANCE. . EVERY STRUCTURE SHALL BE DESIGNED TO
 RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL
 FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR
 WIND LOADS?2014 FBC-B 1604.4 ANALYSIS.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  