| 2016-02-04 11:30:45 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010436 |
| | ADD: 326 FERN ST |
| | CONT: CB & I ENVIRONMENTAL & INFRASTRUCTURE |
| | TEL: 813-612-3678 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. FEB. 04/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) CBI PLANS SHEET # 9 WITH ENCLOSURE PANEL NOTES FOR |
| | THE WALL SYSTEM FL6231.3 THIS PRODUCT APPROVAL WAS |
| | UNDER THE 2007 FBC AND NOTE A CURRENT PRODUCT APPROVAL. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31(G) EXTERIOR COOLER, FREEZERS |
| | 2) CBI PLANS SHEET 8 PROVIDES THE WIND DESIGN AS 170 |
| | VULT EXPOSURE B, THE BUILDING RISK CATEGORY I. FOR A |
| | BUILDING WITH A RISK CATEGORY I THE WIND SPEED IS 160 |
| | VULT, INTERPOLATION BETWEEN THE CONTOUR LINES WILL |
| | PLACE THE WIND SPEED AT 155. THERE IS A DISCREPANCY |
| | BETWEEN THE WIND DESIGN SPEED AND THE RISK CATEGORY. |
| | SEE FBC-B TABLE 1604.5 AND FIGURES FIGURE1609A AND |
| | FIGURE 1609C. |
| | |
| | 3) THE SUBMITTED FLORIDA APPROVAL15491.1-R3. 2014 |
| | FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS |
| | TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION |
| | 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA |
| | RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY |
| | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 4) PLEASE IDENTIFY BY CIRCLING FOR ENCLOSED STRUCTURES, |
| | MAXIMUM ALLOWABLE CLEAR SPAN, THE WIND SPEED, EXPOSURE |
| | LIVE LOADS AND UPLIFT AND DEFLECTION LIMITS AS WELL AS |
| | THE PANEL THICKNESS GAUGE OF SKIN FOR EVALUATION FOR |
| | CODE COMPLIANCE. . EVERY STRUCTURE SHALL BE DESIGNED TO |
| | RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL |
| | FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR |
| | WIND LOADS?2014 FBC-B 1604.4 ANALYSIS. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JAMES A. WITMER CBO |