| Plan Review Notes For Permit 16010427 |
| Permit Number |
16010427 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-07-06 08:40:31 | 3RD REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010427 | | | 7/6/2016 | | | | | | 1) THERE ARE MISSING DIGITAL SIGNATURES ON THE ENERGY | | | GAUGE COMPLIANCE SUBMITTAL (PAGE 3), THE HEAT LOAD | | | CALCULATIONS, THE HEAT LOAD INDEX, THE STRUCTURAL | | | ANALYSIS FROM WALSH P.E. AND SHEETS M3.01 & M3.02. | | | | | | 2) AHU- B3 SHOWN ON SHEET M4.02 IS NOT LISTED IN THE | | | ENERGY CALCULATIONS. | | | | | | 3) PLEASE SEE PAGES 2 & 3 OF THE AC STAND NOA | | | #15-0205.01 AND CIRCLE OR MARK THE SELECTED STAND FRAME | | | ASSEMBLY IN THE DESIGN SCHEDULE ON PAGE 2, AND THE | | | APPLICABLE AC AND AC STAND ATTACHMENT DETAILS ON PAGE | | | 3. | | | | | | 4) THE STRUCTURAL ANALYSIS FROM WALSH ENGINEERING IS | | | INCORRECTLY TITLED BUIDING #2. | | | | | | 5) FINAL APPROVAL OF NATURAL VENTILATION DESIGN FOR THE | | | GARAGES IS PENDING FINAL APPROVAL BY THE WPB FIRE DEPT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|