Plan Review Notes
Plan Review Notes For Permit 16010427
Permit Number 16010427
Review Stop M
Sequence Number 3
Notes
Date Text
2016-07-06 08:40:313RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010427
 7/6/2016
  
 1) THERE ARE MISSING DIGITAL SIGNATURES ON THE ENERGY
 GAUGE COMPLIANCE SUBMITTAL (PAGE 3), THE HEAT LOAD
 CALCULATIONS, THE HEAT LOAD INDEX, THE STRUCTURAL
 ANALYSIS FROM WALSH P.E. AND SHEETS M3.01 & M3.02.
  
 2) AHU- B3 SHOWN ON SHEET M4.02 IS NOT LISTED IN THE
 ENERGY CALCULATIONS.
  
 3) PLEASE SEE PAGES 2 & 3 OF THE AC STAND NOA
 #15-0205.01 AND CIRCLE OR MARK THE SELECTED STAND FRAME
 ASSEMBLY IN THE DESIGN SCHEDULE ON PAGE 2, AND THE
 APPLICABLE AC AND AC STAND ATTACHMENT DETAILS ON PAGE
 3.
  
 4) THE STRUCTURAL ANALYSIS FROM WALSH ENGINEERING IS
 INCORRECTLY TITLED BUIDING #2.
  
 5) FINAL APPROVAL OF NATURAL VENTILATION DESIGN FOR THE
 GARAGES IS PENDING FINAL APPROVAL BY THE WPB FIRE DEPT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  