2016-04-25 13:49:262ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010427
 4/12/16
  
 1) THE 31,000 BTUH AC SYSTEM SHOWN IN THE AC SCHEDULE
 ON SHEET M4.03 IS NOT SHOWN IN THE HEAT LOAD OR ENERGY
 CALCULATIONS.
 2) ENERGY CALCULATION FORM: THE B1.R SYSTEM SPECIFIED
 FOR THE NW CORNER SHOULD BE 16,700 BTUH PER THE HEAT
 LOAD CALCULATIONS AND SUMMARY, HOWEVER IT IS LISTED AT
 21,200 IN THE CALCULATIONS.
 3) ENERGY CALCULATION FORM: THE B SYSTEM SPECIFIED FOR
 THE 4TH FLOOR SE CORNER OF THE BUILDING IN THE CALCS
 SHOULD BE SWITCHED WITH THE C SYSTEM WHICH IS SPECIFIED
 FOR THE NW CORNER.
 4) THE WINDOW GLASS SQUARE FOOTAGE CALCULATIONS ON THE
 HEAT LOAD CALCULATIONS SHOW A MUCH LARGER AMOUNT OF
 GLASS COMPARED TO THE GLASS AREA CALCULATIONS ON THE
 UNIT FLOOR PLANS SHOWN ON SHEETS M4.01, M4.02, AND
 M4.03. PLEASE CLARIFY WHY NO VENTILATION AIR IS SHOWN
 ON THE CALCULATIONS, AND WHY NO LATENT LOADS HAVE BEEN
 CALCULATED FOR INFILTRATION, LIGHTING, AND EQUIPMENT?
 5) THE GARAGE VENTILATION CALCULATIONS ON SHEET M5.01
 INDICATE "NATURAL VENTILATION", HOWEVER THE 100 CFM PER
 CAR IS A MECHANICAL VENTILATION REQUIREMENT INDICATED
 INTABLE 403.3. PLEASE NOTE THAT NATURAL VENTILATION IS
 FOR OCCUPIED SPACES AS INDICATED IN SECTION 401.2,
 HOWEVER PER SECTION 202 DEFINITIONS, A GARAGE IS NOT
 CONSIDERED OCCUPIABLE SPACE. PROVIDE MECHANICAL
 VENTILATION PER TABLE 403.3.
 6) M5.01: THE TRASH ROOM EXHAUST IS NOT CONSIDERED
 ENVIRONMENTAL AIR AND THEREFORE THE OUTLET SHALL BE 10'
 FROM OPERABLE OPENINGS INTO THE BUILDING, AND 10' ABOVE
 THE ADJOINING GRADE. PLEASE REVISE THE NOTE ON THE
 PLAN.
 7) COMMENT #14 FROM THE 1ST REVIEW REQUESTING SITE
 SPECIFIC WIND LOAD ENGINEERING FOR THE ROOF TOP STANDS
 AND CONDENSERS STILL EXISTS: PLEASE COMPLY.
 8) PLEASE SHOW THE DRYER RUN LENGTHS ON THE PLANS AND
 NUMBER OF ELBOWS TO BE USED TO VERIFY COMPLIANCE WITH
 THE DRYER SPECS ON SHEET M5.02.
  