| 2016-05-02 09:55:54 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010427 |
| | ADD: 7150 OKEECHOBEE BLVD. BLDG. TYPE II/ BLDG. # 4. |
| | CONT: ELEV8 CONSTRUCTION CO. / STEVE NAPIER |
| | TEL: 561-891-0414 |
| | E-MAIL: [email protected] |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: TUES. APRIL 19/2016 |
| | ACTION: DENIED |
| | |
| | NOTE: THIS REVIEW IS FOR BUILDING TYPE II, NOT FOR THE |
| | SITE PLAN, OR ANY ASSOCIATED AMENITIES. |
| | |
| | 1) 2ND REQUEST . THE PERMIT APPLICATION VALUE OF |
| | $2,800,000.00 DOLLARS IS LOW. THE AUGUST 2015 ICC |
| | VALUATION TABLES LIST THE VALUE AT: BUILDING TYPE: III |
| | B AT $5,975.852.00 DOLLARS. |
| | NOTE, THE MEP AND ROOFING PERMITS, ARE SUB-PERMITS AND |
| | IF NOT SUBMITTED AT THE TIME OF PERMIT ARE A $80.00 |
| | SUB-PERMIT AND ARE INCLUDED IN THE VALUE OF THE |
| | BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED PERMITS. |
| | PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS FOR THE |
| | BUILDING, SUBMIT A LIST OF PERMITS AND BREAK-OUT THE |
| | VALUE FROM THE TOTAL COST TO DETERMINE THE FINAL |
| | VALUATION OF THE BUILDING PERMIT. |
| | W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT |
| | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, |
| | MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS |
| | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID |
| | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE |
| | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) PLEASE NOTE THIS 4 STORY BUILDING IS CONSIDERED A |
| | THRESHOLD BUILDING BY STATE STATUTE, THRESHOLD BUILDING |
| | FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY |
| | CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN. |
| | THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | 2B) COMPLIED/ MAY 02/16. 2ND REQUEST. THRESHOLD |
| | INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION |
| | SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | 2C) COMPLIEDW.P.B. AMENDMENT 110.3.7.4.4 / 633 FLORIDA |
| | STATUTE. |
| | |
| | 2D) COMPLIED/ MAY 02/16.2ND REQUEST. FOR THE SPECIAL |
| | INSPECTOR PLEASE PROVIDE A RESUME' OF INSPECTION |
| | EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' MUST BE |
| | ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN. |
| | THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE |
| | RESUME'. AFTER THE RESUME' IS REVIEWED, A INTERVIEW |
| | MAYBE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN |
| | INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING |
| | THE ABOVE CRITERIA. |
| | |
| | 2E) COMPLIED ? MAY 02/16. 2ND REQUEST. THE CONTRACTOR |
| | WILL PRODUCE A JOB SUMMARY OR HISTORY FOR THIS TYPE OF |
| | CONSTRUCTION. |
| | |
| | 2F) NOTICE: FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | |
| | 2G) NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE |
| | CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE |
| | INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING |
| | INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT |
| | THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF |
| | JOB, NO INSPECTION ACTIVITY. |
| | |
| | 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6 |
| | THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD |
| | INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED |
| | ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED |
| | FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 3) COMPLIED. ADDRESSING. |
| | |
| | 4) 2ND REQUEST. SOILS REPORT: TIERRA SOUTH FLORIDA FILE |
| | NO. 7111-15-038. IN THIS REPORT THE CONFIRMATION STUDY |
| | WILL INCLUDE SOFT SEDIMENT PROBES AT THE BOTTOM OF THE |
| | EXISTING POND. ONCE BUILDING LOADING INFORMATION |
| | BECOMES AVAILABLE, THEN WE CAN ISSUE A DESIGN ORIENTED |
| | GEOTECHNICAL REPORT THAT MAY INCLUDE REVISING SOME OF |
| | THE RECOMMENDATIONS PRESENTED IN THIS PRELIMINARY |
| | REPORT. IT APPEARS THE BUILDINGS 1 & 2 MAY BE LOCATED |
| | IN A PORTION OF THE EXISTING POND AND FURTHER TESTING |
| | MAY BE REQUIRED. THIS REPORT IS ALSO WRITTEN FOR 5 |
| | STORY BUILDINGS NOT FOUR STORY BUILDINGS THAT MAY ALSO |
| | BECOME A FACTOR FOR LOADING CONCERNS. |
| | 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL. |
| | WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| | OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| | BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 5) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT |
| | FOLDER IS A SURVEY. 2014 FLORIDA BUILDING CODE W 2014 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | SURVEY / FLOOD ZONE |
| | |
| | 6) UNDER THE 2014 ENERGY CODE THIS 4 STORY/ R2 |
| | OCCUPANCY IS CONSIDERED A COMMERCIAL BUILDING. |
| | RESIDENTIAL BUILDING. FOR THE PURPOSE OF THIS CODE, |
| | INCLUDES GROUP R-3 BUILDINGS, AS WELL AS GROUP R-2 AND |
| | R-4 BUILDINGS THREE STORIES OR LESS IN HEIGHT ABOVE |
| | GRADE PLANE. |
| | |
| | 2014 FBC-ENERGY CODE C401.2. COMMERCIAL BUILDINGS SHALL |
| | COMPLY WITH ONE OF THE FOLLOWING: |
| | 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| | 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| | 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | |
| | 7) COMPLIED. |
| | |
| | 8A) ) COMPLIED. SHEET S-4 DOES PROVIDE PRESSURES IN 10 |
| | SQ. FT., 20 SQ. FT., 50 SQ. FT. & 100 SQ. FOR THE WALL |
| | OPENING ZONES FOR ZONES 4 & 5. 2014 FBC-B 1603.1.4 WIND |
| | DESIGN DATA, WIND DESIGN PRESSURES. |
| | |
| | 8B) SEMI -COMPLIED. NOTE THERE WAS A ROOF ZONE LAYOUT |
| | CHART FOR ROOF ZONES 1,2 AND 3 AND THE CALCULATIONS |
| | (STATING VASD) FOR 10 SQ. FT., 20 SQ. FT., 50 SQ. FT. & |
| | 100 SQ. FT. THE ISSUE IS THERE NEEDS TO BE (2) CHARTS |
| | ONE FOR FLAT ROOFS IN VASD AND ONE WITH ASSOCIATED |
| | PRESSURES FOR SLOPED ROOFS 5:12. 2014 FBC-B 1603.1.4 |
| | WIND DESIGN DATA, WIND DESIGN PRESSURES. |
| | |
| | 9A-E) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR THE |
| | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE |
| | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT |
| | SUBMITTED AT THE TIME OF THE |
| | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE |
| | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL |
| | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF |
| | THE BUILDING OFFICIAL. THE REGISTERED DESIGN |
| | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE |
| | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR |
| | REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 9B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014 |
| | FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1 |
| | COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| | AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF |
| | PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP |
| | VENTILATORS |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 9C) DEFERRED SUBMITTALS: 107.3.4.1 THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9D) DEFERRED SUBMITTALS: FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH OPENING. |
| | |
| | 9E) DEFERRED SUBMITTALS: FOR ALL ROOFING PRODUCTS |
| | PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR |
| | ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE |
| | PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS |
| | ALLOWED. IF SO RAS 117 CALCULATIONS ARE REQUIRED BY |
| | EITHER A FLORIDA ARCHITECT OR ENGINEER. |
| | |
| | 9F) 2ND REQUEST. FOR ALL ROOF TOP EQUIPMENT, CURBS OR |
| | A/C STANDS, DETAILED ATTACHMENT TO THE ROOF DECK AS |
| | WELL AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT |
| | ABOVE. 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON |
| | STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE |
| | DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE |
| | INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC |
| | COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL |
| | PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST |
| | THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND |
| | LOADS? |
| | |
| | 10)2ND REQUEST. THIS IS A GENERAL COMMENT THAT WILL |
| | PERTAIN TO ALL FLOORS. PLEASE PROVIDE TEST REPORTS |
| | SHOWING COMPLIANCE WITH: |
| | |
| | 10A)2ND REQUEST. NOTE THIS NOTE APPLIES TO FLOORS 2-4 |
| | ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 10B)2ND REQUEST. THIS NOTE APPLIES TO WALLS ON ALL |
| | FLOORS. WALL TYPES FOUND ON SHEET A8.01, THE WALL TYPES |
| | DO NOT PROVIDE THE REQUIRED STC RATING NOR TEST RESULTS |
| | IN ACCORDANCE WITH: FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 10C) 2ND REQUEST. TYPE III-TYPE V CONSTRUCTION: |
| | FBC-B-2014 720.2 CONCEALED INSTALLATION. |
| | INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN |
| | BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450. |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 11) 1ST FLOOR/ SHEET A2.02.II, |
| | |
| | 11A) 2ND REQUEST, PLEASE SHOW THE WALL TAG ?D? AS |
| | INDICATED IN YOUR RESPONSE. |
| | COMMON CORRIDOR & BOTTOM RIGHT C-1. WALL TYPES NOT |
| | DEPICTED. IN SHEET A4.03 UNIT C,1 THE COMMON CORRIDOR |
| | TO THE RIGHT OF THE ENTRY DOOR IS IDENTIFIED WITH WALL |
| | TAG WALL TYPE (F). JUST TO THE LEFT OF THE ENTRY DOOR |
| | SHEET A2.02.1.1 INDICATES A ROOF DRAIN WALL TYPE IS NOT |
| | IDENTIFIED WITH A WALL TAG. ADDITIONAL INFORMATION |
| | REQUIRED FOR RATED WALL. 107.2.13. 2014 FBC-B 1018.1 & |
| | TABLE 1018.1. FOR THIS TYPE DETAIL THIS COMMENT WILL BE |
| | COMMON FOR ALL FLOORS. |
| | |
| | 11B-D) COMPLIED> |
| | |
| | 11E) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 & |
| | E5.01 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE |
| | PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5 |
| | AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR |
| | OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE |
| | WITH UL 325. IF THERE IS A POWER FAILURE OR A |
| | MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS |
| | HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3. |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 11F)COMPLIED. |
| | |
| | 11G) SEMI-COMPLIED. SHEET E-403 DOES NOT INDICATE THE |
| | SLEEPING ROOMS. THIS COMMENT COMMON TO ALL FLOORS. |
| | PLEASE NOTE WITHIN THIS SET OFF DOCUMENTS THERE ARE NO |
| | LIFE SAFETY SHEETS TO REVIEW. 2014 FBC-B 908.7 CARBON |
| | MONOXIDE PROTECTION. EVERY SEPARATE FOR WHICH A PERMIT |
| | FOR NEW CONSTRUCTION IS ISSUED AND HAVING A FOSSIL-FUEL |
| | BURNING HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED |
| | GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT THAT |
| | EMITS CARBON MONOXIDE AS A BYPRODUCT OF COMBUSTION |
| | SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM |
| | INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING |
| | PURPOSES IN THE NEW AT SUCH OTHER LOCATIONS AS REQUIRED |
| | BY THIS CODE. |
| | 908.7.2 COMBINATION ALARMS. COMBINATION SMOKE/CARBON |
| | MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | THIS COMMENT COMMON TO ALL FLOORS. PLEASE NOTE WITHIN |
| | THIS SET OFF DOCUMENTS THERE ARE NO LIFE SAFETY SHEETS |
| | TO REVIEW. PLEASE IDENTIFY THESE ISSUES ON THE |
| | ARCHITECTURAL FLOOR PLANS SINCE THEY RELATE TO THE |
| | BUILDING CODE REQUIREMENTS. |
| | 2014 FBC-B 908.7 CARBON MONOXIDE PROTECTION. EVERY |
| | SEPARATE FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES IN THE NEW AT SUCH |
| | OTHER LOCATIONS AS REQUIRED BY THIS CODE. |
| | 908.7.2 COMBINATION ALARMS. COMBINATION SMOKE/CARBON |
| | MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | |
| | 11H-11L) COMPLIED. |
| | |
| | 12-14) COMPLIED. |
| | |
| | 15) PROVISO: SHEET A8.02 DETAIL # 11 SHOWS A SLIDING |
| | GLASS DOOR. THE HEIGHT OF THE SLIDING GLASS DOOR SILL |
| | WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT |
| | APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 . |
| | |
| | 16-18) COMPLIED. |
| | |
| | 19) COMPLIED. |
| | |
| | 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |