Plan Review Notes
Plan Review Notes For Permit 16010427
Permit Number 16010427
Review Stop B
Sequence Number 2
Notes
Date Text
2016-05-02 09:55:54BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010427
 ADD: 7150 OKEECHOBEE BLVD. BLDG. TYPE II/ BLDG. # 4.
 CONT: ELEV8 CONSTRUCTION CO. / STEVE NAPIER
 TEL: 561-891-0414
 E-MAIL: [email protected]
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2ND REVIEW
 DATE: TUES. APRIL 19/2016
 ACTION: DENIED
  
 NOTE: THIS REVIEW IS FOR BUILDING TYPE II, NOT FOR THE
 SITE PLAN, OR ANY ASSOCIATED AMENITIES.
  
 1) 2ND REQUEST . THE PERMIT APPLICATION VALUE OF
 $2,800,000.00 DOLLARS IS LOW. THE AUGUST 2015 ICC
 VALUATION TABLES LIST THE VALUE AT: BUILDING TYPE: III
 B AT $5,975.852.00 DOLLARS.
 NOTE, THE MEP AND ROOFING PERMITS, ARE SUB-PERMITS AND
 IF NOT SUBMITTED AT THE TIME OF PERMIT ARE A $80.00
 SUB-PERMIT AND ARE INCLUDED IN THE VALUE OF THE
 BUILDING COST. ALL OTHER SUB-PERMITS ARE FEED PERMITS.
 PLEASE PROVIDE A LIST OF ALL OTHER SUB-PERMITS FOR THE
 BUILDING, SUBMIT A LIST OF PERMITS AND BREAK-OUT THE
 VALUE FROM THE TOTAL COST TO DETERMINE THE FINAL
 VALUATION OF THE BUILDING PERMIT.
 W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
 108.3* BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 2) PLEASE NOTE THIS 4 STORY BUILDING IS CONSIDERED A
 THRESHOLD BUILDING BY STATE STATUTE, THRESHOLD BUILDING
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 2ND REQUEST. 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) COMPLIED/ MAY 02/16. 2ND REQUEST. THRESHOLD
 INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY FL S S 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 2C) COMPLIEDW.P.B. AMENDMENT 110.3.7.4.4 / 633 FLORIDA
 STATUTE.
  
 2D) COMPLIED/ MAY 02/16.2ND REQUEST. FOR THE SPECIAL
 INSPECTOR PLEASE PROVIDE A RESUME' OF INSPECTION
 EXPERIENCE ON PREVIOUS PROJECT. THE RESUME' MUST BE
 ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED HEREIN.
 THE BUILDING OFFICIAL OR HIS DESIGNEE WILL REVIEW THE
 RESUME'. AFTER THE RESUME' IS REVIEWED, A INTERVIEW
 MAYBE SCHEDULED. UNDER NO CIRCUMSTANCES WILL AN
 INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST MEETING
 THE ABOVE CRITERIA.
  
 2E) COMPLIED ? MAY 02/16. 2ND REQUEST. THE CONTRACTOR
 WILL PRODUCE A JOB SUMMARY OR HISTORY FOR THIS TYPE OF
 CONSTRUCTION.
  
 2F) NOTICE: FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
  
 2G) NOTICE ONLY, NO ACTION IS REQUIRED. PLEASE CALL THE
 CITY OF WEST PALM BEACH?S AUTOMATED TELEPHONE
 INSPECTIONS LINE (561) 805-6700) FOR ALL BUILDING
 INSPECTIONS FOR AUDITING OF JOBSITE INSPECTIONS WITHOUT
 THIS THE PERMIT EXPIRES IN 6 MONTHS, ABANDONMENT OF
 JOB, NO INSPECTION ACTIVITY.
  
 2H) NOTICE ONLY, NO ACTION IS REQUIRED. 109.3.6
 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR THRESHOLD
 INSPECTORS #26. ASSURE THAT THE DESIGNER HAS REQUIRED
 ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, APPROVED
 FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3) COMPLIED. ADDRESSING.
  
 4) 2ND REQUEST. SOILS REPORT: TIERRA SOUTH FLORIDA FILE
 NO. 7111-15-038. IN THIS REPORT THE CONFIRMATION STUDY
 WILL INCLUDE SOFT SEDIMENT PROBES AT THE BOTTOM OF THE
 EXISTING POND. ONCE BUILDING LOADING INFORMATION
 BECOMES AVAILABLE, THEN WE CAN ISSUE A DESIGN ORIENTED
 GEOTECHNICAL REPORT THAT MAY INCLUDE REVISING SOME OF
 THE RECOMMENDATIONS PRESENTED IN THIS PRELIMINARY
 REPORT. IT APPEARS THE BUILDINGS 1 & 2 MAY BE LOCATED
 IN A PORTION OF THE EXISTING POND AND FURTHER TESTING
 MAY BE REQUIRED. THIS REPORT IS ALSO WRITTEN FOR 5
 STORY BUILDINGS NOT FOUR STORY BUILDINGS THAT MAY ALSO
 BECOME A FACTOR FOR LOADING CONCERNS.
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) 2ND REQUEST. MISSING FROM THE SUPPORTING DOCUMENT
 FOLDER IS A SURVEY. 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 SURVEY / FLOOD ZONE
  
 6) UNDER THE 2014 ENERGY CODE THIS 4 STORY/ R2
 OCCUPANCY IS CONSIDERED A COMMERCIAL BUILDING.
 RESIDENTIAL BUILDING. FOR THE PURPOSE OF THIS CODE,
 INCLUDES GROUP R-3 BUILDINGS, AS WELL AS GROUP R-2 AND
 R-4 BUILDINGS THREE STORIES OR LESS IN HEIGHT ABOVE
 GRADE PLANE.
  
 2014 FBC-ENERGY CODE C401.2. COMMERCIAL BUILDINGS SHALL
 COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 7) COMPLIED.
  
 8A) ) COMPLIED. SHEET S-4 DOES PROVIDE PRESSURES IN 10
 SQ. FT., 20 SQ. FT., 50 SQ. FT. & 100 SQ. FOR THE WALL
 OPENING ZONES FOR ZONES 4 & 5. 2014 FBC-B 1603.1.4 WIND
 DESIGN DATA, WIND DESIGN PRESSURES.
  
 8B) SEMI -COMPLIED. NOTE THERE WAS A ROOF ZONE LAYOUT
 CHART FOR ROOF ZONES 1,2 AND 3 AND THE CALCULATIONS
 (STATING VASD) FOR 10 SQ. FT., 20 SQ. FT., 50 SQ. FT. &
 100 SQ. FT. THE ISSUE IS THERE NEEDS TO BE (2) CHARTS
 ONE FOR FLAT ROOFS IN VASD AND ONE WITH ASSOCIATED
 PRESSURES FOR SLOPED ROOFS 5:12. 2014 FBC-B 1603.1.4
 WIND DESIGN DATA, WIND DESIGN PRESSURES.
  
 9A-E) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 9B) DEFERRED SUBMITTALS: COMPONENTS & CLADDING. 2014
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS 7 ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 9C) DEFERRED SUBMITTALS: 107.3.4.1 THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9D) DEFERRED SUBMITTALS: FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS
 AND ASSOCIATE PRESSURES FOR EACH OPENING.
  
 9E) DEFERRED SUBMITTALS: FOR ALL ROOFING PRODUCTS
 PLEASE IDENTIFY ALL ROOFING SUB-SYSTEMS AND THEIR
 ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE
 PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS
 ALLOWED. IF SO RAS 117 CALCULATIONS ARE REQUIRED BY
 EITHER A FLORIDA ARCHITECT OR ENGINEER.
  
 9F) 2ND REQUEST. FOR ALL ROOF TOP EQUIPMENT, CURBS OR
 A/C STANDS, DETAILED ATTACHMENT TO THE ROOF DECK AS
 WELL AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT
 ABOVE. 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON
 STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE
 DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE
 INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC
 COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL
 PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST
 THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS?
  
 10)2ND REQUEST. THIS IS A GENERAL COMMENT THAT WILL
 PERTAIN TO ALL FLOORS. PLEASE PROVIDE TEST REPORTS
 SHOWING COMPLIANCE WITH:
  
 10A)2ND REQUEST. NOTE THIS NOTE APPLIES TO FLOORS 2-4
 ONLY. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 10B)2ND REQUEST. THIS NOTE APPLIES TO WALLS ON ALL
 FLOORS. WALL TYPES FOUND ON SHEET A8.01, THE WALL TYPES
 DO NOT PROVIDE THE REQUIRED STC RATING NOR TEST RESULTS
 IN ACCORDANCE WITH: FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 10C) 2ND REQUEST. TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 11) 1ST FLOOR/ SHEET A2.02.II,
  
 11A) 2ND REQUEST, PLEASE SHOW THE WALL TAG ?D? AS
 INDICATED IN YOUR RESPONSE.
 COMMON CORRIDOR & BOTTOM RIGHT C-1. WALL TYPES NOT
 DEPICTED. IN SHEET A4.03 UNIT C,1 THE COMMON CORRIDOR
 TO THE RIGHT OF THE ENTRY DOOR IS IDENTIFIED WITH WALL
 TAG WALL TYPE (F). JUST TO THE LEFT OF THE ENTRY DOOR
 SHEET A2.02.1.1 INDICATES A ROOF DRAIN WALL TYPE IS NOT
 IDENTIFIED WITH A WALL TAG. ADDITIONAL INFORMATION
 REQUIRED FOR RATED WALL. 107.2.13. 2014 FBC-B 1018.1 &
 TABLE 1018.1. FOR THIS TYPE DETAIL THIS COMMENT WILL BE
 COMMON FOR ALL FLOORS.
  
 11B-D) COMPLIED>
  
 11E) PROVISO: THE GARAGES ALL SHOW ON SHEET E1.01 &
 E5.01 CIRCUITRY TO INCLUDE A GARAGE DOOR OPENER. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B 406.3.5
 AUTOMATIC GARAGE DOOR OPENERS. AUTOMATIC GARAGE DOOR
 OPENERS, IF PROVIDED, SHALL BE LISTED IN ACCORDANCE
 WITH UL 325. IF THERE IS A POWER FAILURE OR A
 MECHANICAL BREAKDOWN WITHOUT ANY OTHER MEANS OF EGRESS
 HOW WILL ENTRY INTO A GARAGE BE ACHIEVED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 11F)COMPLIED.
  
 11G) SEMI-COMPLIED. SHEET E-403 DOES NOT INDICATE THE
 SLEEPING ROOMS. THIS COMMENT COMMON TO ALL FLOORS.
 PLEASE NOTE WITHIN THIS SET OFF DOCUMENTS THERE ARE NO
 LIFE SAFETY SHEETS TO REVIEW. 2014 FBC-B 908.7 CARBON
 MONOXIDE PROTECTION. EVERY SEPARATE FOR WHICH A PERMIT
 FOR NEW CONSTRUCTION IS ISSUED AND HAVING A FOSSIL-FUEL
 BURNING HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED
 GARAGE, OR OTHER FEATURE, FIXTURE, OR ELEMENT THAT
 EMITS CARBON MONOXIDE AS A BYPRODUCT OF COMBUSTION
 SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM
 INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING
 PURPOSES IN THE NEW AT SUCH OTHER LOCATIONS AS REQUIRED
 BY THIS CODE.
 908.7.2 COMBINATION ALARMS. COMBINATION SMOKE/CARBON
 MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
 THIS COMMENT COMMON TO ALL FLOORS. PLEASE NOTE WITHIN
 THIS SET OFF DOCUMENTS THERE ARE NO LIFE SAFETY SHEETS
 TO REVIEW. PLEASE IDENTIFY THESE ISSUES ON THE
 ARCHITECTURAL FLOOR PLANS SINCE THEY RELATE TO THE
 BUILDING CODE REQUIREMENTS.
 2014 FBC-B 908.7 CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH
 ROOM USED FOR SLEEPING PURPOSES IN THE NEW AT SUCH
 OTHER LOCATIONS AS REQUIRED BY THIS CODE.
 908.7.2 COMBINATION ALARMS. COMBINATION SMOKE/CARBON
 MONOXIDE ALARMS SHALL BE LISTED AND LABELED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 11H-11L) COMPLIED.
  
 12-14) COMPLIED.
  
 15) PROVISO: SHEET A8.02 DETAIL # 11 SHOWS A SLIDING
 GLASS DOOR. THE HEIGHT OF THE SLIDING GLASS DOOR SILL
 WILL BE DETERMINED BY THE SLIDING GLASS DOOR PRODUCT
 APPROVAL AND ASSOCIATED PRESSURES. SHEET A8.02 .
  
 16-18) COMPLIED.
  
 19) COMPLIED.
  
 20) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 21) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  