| 2016-02-10 15:55:50 | 1ST REVIEW: FBC 2014 MECHANICAL |
| | PERMIT #15120897 |
| | 2/10/2016 |
| | |
| | 1) MULTI-FAMILY BUILDINGS OVER THREE STORIES IN HEIGHT |
| | SHALL COMPLY WITH CHAPTER 4, COMMERCIAL ENERGY |
| | EFFICIENCY- FBC-14 ENERGY CONSERVATION. PROVIDE AC |
| | COOLING AND HEATING LOAD CALCULATIONS IN ACCORDANCE |
| | WITH THE PROCEDURES DESCRIBED IN THE ASHRAE/ACCA |
| | STANDARD 183 OR ACCA MANUAL N- SEE SECTION C403.2.1. |
| | 2) MANY PAGES ARE MISSING FROM THE SUBMITTED ENERGY |
| | CALCULATIONS INCLUDING THE COVER SHEETS, THE SIGNATURE |
| | PAGE, AND THE MANDATORY COMPLIANCE CHECKLIST. PLEASE |
| | PROVIDE A COMPLETE COMPLIANCE SUBMITTAL. |
| | 3) THE AC SYSTEM ID LABELS IN THE ENERGY CALCULATIONS |
| | DO NOT COMPLETELY MATCH THE ID LABELS SHOWN ON THE |
| | SCHEDULES- SHEETS M.401, 402, & 403. |
| | 4) PROVIDE VENTILATION CALCULATIONS FOR THE GARAGES AND |
| | INDICATE HOW THEY WILL BE VENTILATED- NATURAL OR |
| | MECHANICAL VENTILATION? |
| | 5) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| | TRASH ROOMS. |
| | 6) PROVIDE CLEARANCE DISTANCE MEASUREMENTS FOR THE |
| | TRASH ROOM EXHAUST OUTLETS IN COMPLIANCE WITH SECTION |
| | 501.3.1 FBC-14 MECHANICAL. |
| | 7) INDICATE HOW THE ELEVATOR MACHINE ROOM AC SYSTEMS |
| | WERE SIZED- PROVIDE CALCULATIONS. |
| | 8) AC FLOOR PLANS M.401, 402, 403: PLEASE PLACE THE |
| | TYPICAL NOTES SHOWN ON M4.01 ON ALL FLOOR PLAN SHEETS |
| | WITH THE ADDED MODIFICATIONS LISTED BELOW. |
| | 9) M.401, 402, 403: SHOW THE REQUIRED MINIMUM 4" |
| | CLEARANCE SPACES AROUND THE AIR HANDLERS IN THE CLOSET- |
| | SECTION 603.1.1. |
| | 10) M4.01, 402, 403: INDICATE METAL LOUVERED DOORS AT |
| | AC CLOSETS- SECTION C403.2.7.2 FBC-14 ENERGY |
| | CONSERVATION. |
| | 11) M.401, 402, 403: INDICATE THE TYPE AND SIZE OF BATH |
| | EXHAUST VENTING. |
| | 12) M.402: REFER TO 601.5 AND INCREASE THE TRANSFER |
| | DUCT SIZES FROM BEDROOM #2 ON ALL FLOOR PLANS TO 1.5 |
| | TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY DUCTS |
| | ENTERING THE ROOMS. |
| | 13) M.403: REFER TO 601.5 AND INCREASE THE TRANSFER |
| | DUCT SIZES FROM THE BEDROOMS (WHERE DEFICIENT) TO 1.5 |
| | TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY DUCTS |
| | ENTERING THE ROOMS. |
| | 14) M.402 & 403: PLEASE CLARIFY THE NOTE "FOR INTERIOR |
| | UNITS ONLY" PERTAINING TO THE SUPPLY DUCTS BY THE |
| | BEDROOMS. |
| | 15) M.501: PROVIDE FLEX DUCT CONNECTION, SEALING, AND |
| | HANGING DETAILS- SECTION C403.2.7.2 FBC-14 ENERGY |
| | CONSERVATION. |
| | 16) M.502: THE NOA NUMBER LISTED ON THE PLAN FOR THE AC |
| | STAND IS EXPIRED. PLEASE NOTE SITE-SPECIFIC WIND LOAD |
| | ENGINEERING IS REQUIRED FOR TIE DOWN OF THE ROOF TOP AC |
| | CONDENSERS AND CONDENSER STANDS. PROVIDE A CURRENT NOA |
| | WITH A REVIEW AND APPROVAL SIGNATURE BY THE ENGINEER OF |
| | RECORD. THE EOR SHALL PROVIDE THE WIND LOAD DESIGN |
| | CRITERIA ON THE PLAN AS OUTLINED BELOW AND CIRCLE, |
| | HIGHLIGHT, OR OTHERWISE MARK ALL NOTES, DETAILS ETC. ON |
| | THE NOA APPLICABLE TO THE INSTALLATIONS. |
| | |
| | WIND DESIGN CRITERIA |
| | 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | A) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | B) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | C) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | D) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | E) COMPONENTS & CLADDING PRESSURES POSITIVE & NEGATIVE |
| | TABLE 1609.2(2). |
| | F) COMPONENTS & CLADDING/ 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | |
| | 17) REFRIGERANT PIPING: A) PROVIDE RISER DRAWINGS. B) |
| | PROVIDE THE TYPE AND THICKNESS OF PIPING INSULATION, |
| | THE FLAME SPREAD RATING, AND HOW IT WILL BE PROTECTED |
| | FROM UV AND WEATHERING DEGRADATION ON THE ROOF TOP. C) |
| | SUBMIT SPECS REVIEWED AND APPROVED WITH SIGNATURE BY |
| | THE EOR. |
| | 18) PROVIDE VENTILATION CALCULATIONS FOR THE HOISTWAY |
| | SHAFTS AND SUBMIT A CURRENT FLORIDA PRODUCT APPROVAL OR |
| | MIAMI-DADE NOA FOR THE SHAFT LOUVER REVIEWED AND |
| | APPROVED BY THE EOR- SEE SECTION 3004 FBC-14 BUILDING. |
| | 19) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | KITCHEN HOODS REVIEW AND APPROVED WITH SIGNATURE BY THE |
| | EOR. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |