| Plan Review Notes For Permit 16010415 |
| Permit Number |
16010415 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-26 17:53:48 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF ELECTRICAL LOAD CALCULATIONS TO | | | SHOW THAT THE EXISTING SERVICE IS ADEQUATE FOR THE | | | ADDITION OF THE ELECTRIC POOL HEATER. FBCR-E3602.2 AND | | | E4206.12 | | | | | | 2) PLANS SPECIFY A GULFSTREAM HE-125RA 125K BTU HEAT | | | PUMP AND THE SPECS THAT WERE SUBMITTED ARE FOR A | | | HAYWARD HEAT PUMP. FBC 107.2.1 | | | | | | |
|