| 2016-03-14 06:58:55 | 1) SHT.A3.0 - MEN'S RESTROOM NOTES "EXISTING TO REMAIN, | | | NO WORK REQD." BUT THE PLUMBING PLANS SHOW A NEW SHOWER | | | IN THE MEN'S RESTROOM. CLARIFY. | | | 2) SHOW THE SHOWER AND THE SHOWER DIMENSIONS ON THE | | | ARCHITECTURAL PLANS. THE SHOWER SHALL COMPLY WITH THE | | | FL. ACCESSIBILITY CODE SEC.213.2,608.2.2, 608.2.3. | | | 3) SUBMIT A SANITARY AND WATER RISER FOR THE SHOWER. | | | FBC 107.3.5.1.3. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|