2016-03-14 06:58:551) SHT.A3.0 - MEN'S RESTROOM NOTES "EXISTING TO REMAIN,
 NO WORK REQD." BUT THE PLUMBING PLANS SHOW A NEW SHOWER
 IN THE MEN'S RESTROOM. CLARIFY.
 2) SHOW THE SHOWER AND THE SHOWER DIMENSIONS ON THE
 ARCHITECTURAL PLANS. THE SHOWER SHALL COMPLY WITH THE
 FL. ACCESSIBILITY CODE SEC.213.2,608.2.2, 608.2.3.
 3) SUBMIT A SANITARY AND WATER RISER FOR THE SHOWER.
 FBC 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW