| Plan Review Notes For Permit 16010403 |
| Permit Number |
16010403 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-03-11 08:57:13 | 2ND REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010403 | | | 3/11/16 | | | | | | 1) 2ND REQUEST FOR AC CALCULATIONS FOR THE AHU/CU-1 | | | SYSTEM- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. | | | 2) CLARIFY HOW SUPPLY AIR TO THE AREAS OF STATIONS B, | | | C, D, E, & F IS BEING RETURNED TO THE AIR HANDLER. IT | | | APPEARS BY THE ARCHITECTURAL DETAILS THAT THE WALLS | | | ENCLOSING THE OFFICE WALLS RUN TO THE CEILINGS AND | | | THERE IS A SOLID WOOD DOOR AT THE MECHANICAL ROOM | | | ENTRANCE. IS THE AA/775 RETURN GRILL IN THE OFFICE TO | | | BE USED BECAUSE IT APPEARS TO BE NOT ACCESSIBLE FOR THE | | | AIR TO RETURN THROUGH? PLEASE NOTE THAT IF THE MECH | | | CLOSET IS A PLENUM CHAMBER THE WOOD DOOR SHOWN ON THE | | | SCHEDULE MUST BE CHANGED TO A NON-COMBUSTIBLE TYPE- | | | SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION. PLEASE | | | SEE SECTION 601.2 FBC-14 MECHANCIAL: CORRIDORS SHALL | | | NOT SERVE AS RETURN DUCTS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|