| 2016-03-15 06:23:42 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16010403 |
| | ADD: 2255 PALM BEACH LAKES BLVD |
| | CONT: MCCABE BROTHERS |
| | TEL: 561-278-0404 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: TUES. MARCH 15/ 2016 |
| | ACTION: DENIED |
| | |
| | 1) NEW COMMENT, DISCREPANCY IN PLANS, 107.2.1.3. THE |
| | A5.0 SHEET AND P2.1 SHEET DO NOT MATCH. THE NEW P2.1 |
| | SHEET SHOWS A NEW SHOWER IN THE |
| | 1ST FLOOR MENS RESTROOMS WHERE THE ARCHITECTURAL SHEETS |
| | DO NOT. IF THIS IS A REVISION TO THE PLANS THEN THE |
| | SHOWER WILL NEED TO BE ACCESSIBLE SHOW COMPLIANCE WITH |
| | THE 2014 FBC-ACCESSIBILITY CODE: |
| | |
| | 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE TOILET |
| | ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH |
| | 603. WHERE BATHING ROOMS ARE PROVIDED, EACH BATHING |
| | ROOM SHALL COMPLY WITH 603. |
| | |
| | 213.3 PLUMBING FIXTURES AND ACCESSORIES. PLUMBING |
| | FIXTURES AND ACCESSORIES PROVIDED IN A TOILET ROOM OR |
| | BATHING ROOM REQUIRED TO COMPLY WITH 213.2 SHALL COMPLY |
| | WITH 213.3. |
| | |
| | 213.3.6 BATHING FACILITIES. WHERE BATHTUBS OR SHOWERS |
| | ARE PROVIDED, AT LEAST ONE BATHTUB COMPLYING WITH 607 |
| | OR AT LEAST ONE SHOWER COMPLYING WITH 608 SHALL BE |
| | PROVIDED. |
| | |
| | 608.1 GENERAL. SHOWER COMPARTMENTS SHALL COMPLY WITH |
| | 608. 608.2 SIZE AND CLEARANCES FOR SHOWER COMPARTMENTS. |
| | SHOWER COMPARTMENTS SHALL HAVE SIZES AND CLEARANCES |
| | COMPLYING WITH 608.2. |
| | |
| | 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS. TRANSFER |
| | TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES (915 MM) BY |
| | 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS MEASURED AT |
| | THE CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 36 |
| | INCH (915 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE |
| | SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES (915 MM) |
| | WIDE MINIMUM BY 48 INCHES (1220 MM) LONG MINIMUM |
| | MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED. |
| | |
| | 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. |
| | STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30 |
| | INCHES (760 MM) WIDE MINIMUM BY 60 INCHES (1525 MM) |
| | DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER |
| | POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES |
| | (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER |
| | COMPARTMENT. |
| | |
| | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |