Plan Review Notes
Plan Review Notes For Permit 16010403
Permit Number 16010403
Review Stop B
Sequence Number 2
Notes
Date Text
2016-03-15 06:23:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010403
 ADD: 2255 PALM BEACH LAKES BLVD
 CONT: MCCABE BROTHERS
 TEL: 561-278-0404
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 15/ 2016
 ACTION: DENIED
  
 1) NEW COMMENT, DISCREPANCY IN PLANS, 107.2.1.3. THE
 A5.0 SHEET AND P2.1 SHEET DO NOT MATCH. THE NEW P2.1
 SHEET SHOWS A NEW SHOWER IN THE
 1ST FLOOR MENS RESTROOMS WHERE THE ARCHITECTURAL SHEETS
 DO NOT. IF THIS IS A REVISION TO THE PLANS THEN THE
 SHOWER WILL NEED TO BE ACCESSIBLE SHOW COMPLIANCE WITH
 THE 2014 FBC-ACCESSIBILITY CODE:
  
 213.2 TOILET ROOMS AND BATHING ROOMS. WHERE TOILET
 ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL COMPLY WITH
 603. WHERE BATHING ROOMS ARE PROVIDED, EACH BATHING
 ROOM SHALL COMPLY WITH 603.
  
 213.3 PLUMBING FIXTURES AND ACCESSORIES. PLUMBING
 FIXTURES AND ACCESSORIES PROVIDED IN A TOILET ROOM OR
 BATHING ROOM REQUIRED TO COMPLY WITH 213.2 SHALL COMPLY
 WITH 213.3.
  
 213.3.6 BATHING FACILITIES. WHERE BATHTUBS OR SHOWERS
 ARE PROVIDED, AT LEAST ONE BATHTUB COMPLYING WITH 607
 OR AT LEAST ONE SHOWER COMPLYING WITH 608 SHALL BE
 PROVIDED.
  
 608.1 GENERAL. SHOWER COMPARTMENTS SHALL COMPLY WITH
 608. 608.2 SIZE AND CLEARANCES FOR SHOWER COMPARTMENTS.
 SHOWER COMPARTMENTS SHALL HAVE SIZES AND CLEARANCES
 COMPLYING WITH 608.2.
  
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS. TRANSFER
 TYPE SHOWER COMPARTMENTS SHALL BE 36 INCHES (915 MM) BY
 36 INCHES (915 MM) CLEAR INSIDE DIMENSIONS MEASURED AT
 THE CENTER POINTS OF OPPOSING SIDES AND SHALL HAVE A 36
 INCH (915 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE
 SHOWER COMPARTMENT. CLEARANCE OF 36 INCHES (915 MM)
 WIDE MINIMUM BY 48 INCHES (1220 MM) LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
  
 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30
 INCHES (760 MM) WIDE MINIMUM BY 60 INCHES (1525 MM)
 DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES
 (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  