Plan Review Notes
Plan Review Notes For Permit 16010403
Permit Number 16010403
Review Stop M
Sequence Number 1
Notes
Date Text
2016-01-21 14:39:021ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010403
 1/21/16
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW MEZZANINE AND LUNCHROOM SYSTEM- REFERENCE SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION, CALCULATION OF
 HEATING AND COOLING LOADS.
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 RENOVATED AREAS IN ACCORDANCE WITH SECTION 809.1 FBC-14
 EXISTING BUILDING CODE, AND TABLE 403.3 FBC-14
 MECHANICAL.
 3) SUBMIT THE NOA FOR THE CONDENSER STAND WITH A REVIEW
 AND APPROVAL SIGNATURE FROM THE ENGINEER OF RECORD.
 4) ADVISORY: A NON-COMBUSTIBLE DOOR IS REQUIRED FOR
 MECHANICAL CLOSETS THAT FORM THE PRIMARY AIR
 CONTAINMENT FOR AIR DISTRIBUTION SYSTEMS- SECTION
 C403.2.7.2 FBC-14 ENERGY CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  