| Plan Review Notes For Permit 16010403 |
| Permit Number |
16010403 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-01-21 14:39:02 | 1ST REVIEW: FBC 2014 MECHANICAL | | | PERMIT #16010403 | | | 1/21/16 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW MEZZANINE AND LUNCHROOM SYSTEM- REFERENCE SECTION | | | C403.2.1 FBC-14 ENERGY CONSERVATION, CALCULATION OF | | | HEATING AND COOLING LOADS. | | | 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE | | | RENOVATED AREAS IN ACCORDANCE WITH SECTION 809.1 FBC-14 | | | EXISTING BUILDING CODE, AND TABLE 403.3 FBC-14 | | | MECHANICAL. | | | 3) SUBMIT THE NOA FOR THE CONDENSER STAND WITH A REVIEW | | | AND APPROVAL SIGNATURE FROM THE ENGINEER OF RECORD. | | | 4) ADVISORY: A NON-COMBUSTIBLE DOOR IS REQUIRED FOR | | | MECHANICAL CLOSETS THAT FORM THE PRIMARY AIR | | | CONTAINMENT FOR AIR DISTRIBUTION SYSTEMS- SECTION | | | C403.2.7.2 FBC-14 ENERGY CONSERVATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|