2016-01-26 09:30:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010403
 ADD: 2255 PALM BEACH LAKES BLVD
 CONT: MCCABE BROTHERS
 TEL: 561-278-0404
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 26/ 2016
 ACTION: DENIED
  
 1) THE COVERSHEET A1.0:
 1A) THE PLANS INDICATE THEY WERE DESIGNED TO THE 2010
 FBC. PLEASE BE AWARE THE EDITION OF THE CODE CHANGED ON
 JUNE 30/ 2015 TO THE 5TH EDITION (2014) OF THE FLORIDA
 BUILDING CODE.
  
 1B) ONLY THE COVERSHEET, A1.0 HAS AN ORIGINAL SIGNATURE
 AND SEAL THE REST OF THE SHEETS WITHIN THE SET OF PLAN
 HAVE SEALS AND COPIED SIGNATURES.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS.
 2) SHEET A2.0:
 2A) THIS BUILDING IS BEING CLASSIFIED AS A TYPE II
 BUILDING. PLEASE IDENTIFY UNDER WHICH CODE YOU ARE
 CLASSIFYING THIS BUILDING TYPE AS A TYPE II BUILDING.
 UNDER THE 2001 FBC-B THE BUILDING TYPE II WAS
 RECLASSIFIED AS A BUILDING TYPE IA UNDER THE 2004 FBC
 AND SINCE. SEE 2007 CODE COMMENTARY FIGURE 600.
  
 2B) IN THE OCCUPANCY CLASSIFICATIONS WAREHOUSE 33,112
 SQ. FT./500= 66 OCCUPANTS, & BUSINESS 2528 SQ.
 FT./100=25 OCCUPANTS. PLEASE BE AWARE YOU ALWAYS ROUND
 UP TO THE NEXT WHOLE PERSON YOU HAVE NO PARTIAL PEOPLE.
 2014 FBC-B 1004.1.
  
 BOAF INFORMAL CODE INTERPRETATION
 DATE: TUE DEC 18 2007
 REPORT #: 5479
 CODE: BUILDING
 SECTION: 1004.1.2
 QUESTION:
 IS IT THE INTENT OF SECTION 1004.1.2 TO ALLOW THE
 LARGEST NUMBER COMPUTED IN ACCORDANCE WITH
 TABLE 1004.1.2 TO BE ROUNDED TO THE NEAREST WHOLE
 NUMBER? COMMENT: FOR EXAMPLE, A
 BUSINESS OCCUPANCY IN A BUILDING WITH 3215 GROSS SQUARE
 FEET, CALCULATED OCCUPANCY LOAD
 WOULD BE 32.15 WOULD I ROUND DOWN TO 32 OCCUPANTS OR
 WOULD I BE REQUIRED TO ROUND UP TO
 33 OCCUPANTS
 ANSWER:
 ROUND UP TO 33
 COMMENTARY:
 OCCUPANTS ONLY COME AS A WHOLE.
  
 2C) WITHIN THIS SET OF PLANS THERE IS NO LIFE SAFETY
 PLAN THAT PROVIDES:
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 (6.) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING
 REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED(SEPARATION).
 OCCUPANT LOAD AND EGRESS CAPACITIES
 EARLY WARNING
 )7.) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS
  
 2D) PLEASE BREAK DOWN THE OCCUPANT LOADS FOR THE 1ST
 FLOOR AND 2ND FLOOR (MEZZANINE) BY FLOOR AND BY
 OCCUPANCY TYPE. THE 2ND FLOOR, (MEZZANINE) INDICATES
 555 SQ. FT. OF CHANGE OF OCCUPANCY, BUT DOES NOT
 INDICATE THE OVERALL SQUARE FEET OF THE 2ND FLOOR
 (MEZZANINE). I HAVE ADDED UP THE SQUARE FOOTAGE OF THE
 2ND FLOOR AREA AND IS APPROXIMATELY 1050 SQUARE FEET.
 1050/100= 11 OCCUPANTS. THE AREA BELOW THE 2ND FLOOR IS
 AN ENCLOSED AREA AND DOES NOT COMMUNICATE (THE AIR)
 WITH A MEZZANINE, NOR DOES THE 2ND FLOOR WHICH NOW IS
 FULLY ENCLOSED. THE OCCUPANT LOAD IS GREATER THAN 10
 AND DOES NOT MEET THE EXCEPTIONS OF 505.2.3 AND WILL
 NEED TO BE CONSIDERED A 2ND FLOOR.
 PLEASE REVIEW SECTIONS IN THE 2014 FBC-B:
 FBC-B 1009.3 EXCEPTION # 1.
 FBC-B 1016.3.1
 FBC-B TABLE 1016.2 ALLOWABLE TRAVEL DISTANCE.
  
 NOTE THE TABLE 508.4 BUSINESS AND S1 OCCUPANCIES
 INDICATES NO OCCUPANCY SEPARATION. PLEASE REVIEW BOAF
 INFORMAL INTERPRETATION: 7357
  
 DATE: TUE JUL 1 2014
 REPORT: 7357
 CODE: BUILDING CODE YEAR: 2010
 SECTION: TABLE 508.4
 QUESTION:
 IS IT THE INTENT OF TABLE 508.4 TO REQUIRE A (1HR (S),
 2HR (NS)) SEPARATION BETWEEN B AND S-2 OCCUPANCY AND NO
 SEPARATION
 REQUIREMENT BETWEEN B AND S-1 OCCUPANCY?
 COMMENT:
 PER CHAPTER 3, S-2 OCCUPANCY ARE DEFINED AS LOW- HAZARD
 STORAGE, WHERE AS S-1 OCCUPANCY IS DEFINED AS
 MODERATE-HAZARD OCCUPANCY. THE STORED MATERIALS LIST
 FOR S-1 OCCUPANCY IS MUCH MORE HAZARDOUS THAN THE LIST
 FOR S-2 OCCUPANCY AND ONE WOULD THINK THAT THE S-1
 OCCUPANCY WOULD REQUIRE THE SEPARATION AND THE S-2
 OCCUPANCY WOULD NOT.
 ANSWER:
 BASED ON THE INFORMATION REVIEWED, IT APPEARS YOU ARE
 CORRECT THAT A TYPO EXISTS. THE BEST APPROACH FOR THIS
 PARTICULAR ISSUE WOULD BE EITHER A FORMAL
 INTERPRETATION WHICH HAS STANDING OR A DEC STATEMENT
 FROM THE FLORIDA BUILDING COMMISSION. PLEASE SEE THE
 COMMENTARY BELOW.
 COMMENTARY:
 TABLE 508.4 DOES APPEAR TO HAVE A TYPO. THE 2001
 FLORIDA BUILDING CODE, TABLE 704.1 REQUIRED A 3 HOUR
 SEPARATION FOR S1 AND A 2 HOUR SEPARATION FOR S2. IN
 THE 2004 CODE TABLE 706.3.7 ALSO REQUIRES 3 HOURS FOR
 S1 AND 2 HOURS FOR S2. THE TYPO APPEARS TO HAVE BEEN
 INTRODUCED WITH TABLE 508.4 IN THE 2007 CODE. TABLE
 508.4 APPEARS TO HAVE BEEN WRONG SINCE ITS INCEPTION.
 SUBMITTING A REQUEST FOR A FORMAL INTERPRETATION WOULD
 PERMIT APPLICATION OF CORRECTION TO THIS ISSUE UNTIL A
 CODE CHANGE CAN BE MADE, IF IT IS NOT ALREADY IN THE
 WORKS.
  
 YOU CAN?T TAKE THE OCCUPANTS OF A BUSINESS OCCUPANCY
 THROUGH A OCCUPANCY WITH A HIGHER OCCUPANCY HAZARD
 WITHOUT THE STAIR BEING IN A 1 HOUR ENCLOSURE.
  
 2E) THE TABLE FOR FIRE RESISTANCE RATINGS FOR BUILDING
 ELEMENTS, INDICATES ZERO HOURS FIRE RATING FOR THE ROOF
 CONSTRUCTION AND ASSOCIATED SECONDARY MEMBERS. IN THE
 2014 FBC-B TABLE 601 INDICATES FOR BUILDING TYPE 1B OR
 IIA, 1 HOUR FIRE RATING REQUIRED, MEZZANINE LEVEL, SEE
 EXCEPTION ?B?.
  
 2F) THIS IS AN EXISTING BUILDING AND IS SUBJECT TO THE
 2014 EXISTING BUILDING CODE SECTION 301.1. THE DESIGNER
 OF RECORD WILL NEED TO SHOW THE PLANS WERE DESIGNED
 UNDER ONE OF THE METHODS LISTED, 301.1.1THROUGH
 301.1.3. IF THE WORK AREA METHOD IS PICKED THEN TO WHAT
 LEVEL OF ALTERATION WERE THE PLANS DESIGNED?
  
 2G) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S.
 THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS?
 RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL
 ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S.
 AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE-
 ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION
 TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO:
 * DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 3) SHEET A4.0 :
 3A) WITH AN OCCUPANT LOAD OF 11 ON THE 2ND FLOOR PLEASE
 PROVIDE AN ACCESSIBLE MEANS OF EGRESS TO THE 2ND FLOOR.
 2014 FBC-ACCESSIBILITY CODE 201.1.1 VERTICAL
 ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
  
 3B) 2014 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF
 EGRESS SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION). SEE AREA OF RESCUE
 ASSISTANCE AND REQUIREMENTS.
  
 3C) ON THE 2ND FLOOR LEVEL THE NEW STAIR SHOWS AN AREA
 OF RESCUE ASSISTANCE BEHIND THE DOOR. HOW IS THE PERSON
 IN THE WHEELCHAIR TO GAIN ENTRY TO THE AREA OF RESCUE
 ASSISTANCE? ADDITIONAL INFORMATION IS REQUIRED.
 107.2.1.3.
  
 3D) THE WINDOWS AND DOORS THAT ARE IN THE OCCUPANCY
 SEPARATION WALL, WHERE TABLE 508.4 REQUIRES A 1 HOUR
 FIRE SEPARATION, PLEASE PROVIDE HOW COMPLIANCE WITH
 OPENING PROTECTIVE IN TABLE 716.5 OTHER FIRE BARRIERS ?
 HR. FIRE RATING.
  
 3E) THE 1 HR. OCCUPANCY SEPARATION WALL (FIRE BARRIER)
 WILL NEED TO SHOW THE ONE HOUR FIRE RATING PER TABLE
 504.8. PLEASE ALSO SHOW COMPLIANCE WITH :
 FBC-B 707.5 CONTINUITY.
 FIRE BARRIERS SHALL EXTEND FROM THE TOP OF THE
 FOUNDATION OR FLOOR/CEILING ASSEMBLY BELOW TO THE
 UNDERSIDE OF THE FLOOR OR ROOF SHEATHING, SLAB OR DECK
 ABOVE AND SHALL BE SECURELY ATTACHED THERETO. SUCH FIRE
 BARRIERS SHALL BE CONTINUOUS THROUGH CONCEALED SPACE,
 SUCH AS THE SPACE ABOVE A SUSPENDED CEILING. JOINTS AND
 VOIDS AT INTERSECTIONS SHALL COMPLY WITH SECTIONS 707.8
 AND 707.9
  
 FBC-B 707.5.1 SUPPORTING CONSTRUCTION.
 THE SUPPORTING CONSTRUCTION FOR A FIRE BARRIER SHALL BE
 PROTECTED TO AFFORD THE REQUIRED FIRE-RESISTANCE RATING
 OF THE FIRE BARRIER SUPPORTED. HOLLOW VERTICAL SPACES
 WITHIN A FIRE BARRIER SHALL BE FIREBLOCKED IN
 ACCORDANCE WITH SECTION 718.2 AT EVERY FLOOR LEVEL.
  
 4) SHEET A6.0 SHOWS MICROWAVES AT A ELEVATION EQUAL TO
 THE UPPER CABINETS. PLEASE SHOW COMPLIANCE WITH THE
 2014 FBC-ACCESSIBILITY CODE: OPERABLE PARTS SHALL
 COMPLY WITH 309.
  
 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE PROVIDED.
  
 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN ONE
 OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  